Plan Review Notes
Plan Review Notes For Permit 05100947
Permit Number 05100947
Review Stop M
Sequence Number 2
Notes
Date Text
2006-02-03 00:00:00 
 *** DENIED ***
 1) ENERGY COLCULATIONS NEED TO BE SIGNED
 BY OWNER/ AGENT.
  
 2) MANUAL J CALCULATIONS ARE ONLY
 SHOWING NEW ADDITION SQUARE FEET ONLY
 BUT THEENTIRE HOUSE IS BEING AIR
 CONDITIONED SO SQUARE FEET NEEDS TO BE
 FOR ENTIRE HOUSE. AND PLEASE HAVE MANUAL
 'J' SHOWING CFM'S AND DUCT SIZES TO ALL
 ROOMS.
  
 3) NEED TO PROVIDE TWO COPYS OF ALL
 PAPER-WORK.
  
 4) EQUIPMENT LIST OR MECH. PLANS IS
 CALLING FOR 10.3 SEER (ENERGY CAL'S 12
 SEER), UNIT #1 3 TON ( TOTAL BTU'S
 45,500 IS INCORRECT), UNIT #2 2 TON
 (TOTAL BTU'S 45,500 IS INCORRECT).
 PLEASE CORRECT INFORMATION ON EQUIP.
 LIST TO COINCIDE WITH NEW MANUAL 'J'.
  
 5) AHU #1, 10" SUPPLY AIR DUCT FROM AHU
 IS TO SMALL FOR A 3 TON UNIT.
  
 6) AHU #1, RETURN AIR GRILL IS NOT
 SIZED.
  
 7) NO RETURN AIR IS PROVIDED FOR BEDROOM
 #1, EXISTING BEDROOM #1 & #2 SEE NOTE#8.
  
 8) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 9) PLEASE NOTE ON MECH. PLANS IF ALL
 DUCT WORK IS NOT NEW, THEN NOTE WHAT
 DUCT WORK IS EXISTING.
  
 10)AHU #2, 12" RETURN AIR DUCT AND 14X14
 RETURN AIR GRILL ARE TO SMALL FOR A 2
 TON UNIT.
  
 11) PLEASE SEE HIGH-LIGHTS ON MECH.
 PLANS AND CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  