2005-11-17 00:00:00*** DENIED ***
 1) NEED ENERGY CALCULATIONS AND MANUAL
 'J' CALCULATIONS,PER 2004 FBC
 13-600.1.ABC .
 2)GRILL SIZES AND CFM'S NOT SHOWING.
 3) PLEASE CHECK A/C EQUIP. INFO. AND
 CORRECT (SHOWING FOR TWO, 4 TON A/C
 SYSSTEMS.
 4) PLEASE CHECK AND CORRECT DUCT SIZES
 AT AHU'S.
 5)PLEASE CHECK AND CORRECT SQUARE
 FOOTAGE INFO. ON PAGE 4.1 OF PLANS.
 6) IF KITCHEN RANGE IS A DOWN DRAFT
 PLAESE SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS, AND SHOW EXHUST DUCT ON
 PLANS.
 7) PLEASE SHOW LOCATION OF CONDENSER
 UNITS ON PLANS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.