| Plan Review Notes For Permit 05100947 |
| Permit Number |
05100947 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-17 00:00:00 | *** DENIED *** | | | 1) NEED ENERGY CALCULATIONS AND MANUAL | | | 'J' CALCULATIONS,PER 2004 FBC | | | 13-600.1.ABC . | | | 2)GRILL SIZES AND CFM'S NOT SHOWING. | | | 3) PLEASE CHECK A/C EQUIP. INFO. AND | | | CORRECT (SHOWING FOR TWO, 4 TON A/C | | | SYSSTEMS. | | | 4) PLEASE CHECK AND CORRECT DUCT SIZES | | | AT AHU'S. | | | 5)PLEASE CHECK AND CORRECT SQUARE | | | FOOTAGE INFO. ON PAGE 4.1 OF PLANS. | | | 6) IF KITCHEN RANGE IS A DOWN DRAFT | | | PLAESE SUBMIT DETAILED MANUFACTURE'S | | | SPECIFICATION'S AND INSTALLATION | | | INSTRUCTIONS, AND SHOW EXHUST DUCT ON | | | PLANS. | | | 7) PLEASE SHOW LOCATION OF CONDENSER | | | UNITS ON PLANS. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|