Plan Review Notes
Plan Review Notes For Permit 05100947
Permit Number 05100947
Review Stop E
Sequence Number 1
Notes
Date Text
2005-11-17 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE LOCATION OF THE
 METER AND PANEL SHOWN ON THE RISER, ON
 THE PLAN.
  
 2} PLEASE SEE THERE ARE TWO DESIGNATIONS
 FOR THE SAME FEEDER ON THE RISER, ONE
 WITH 3 #!, AND ONE WITH 3 2/0. PLEASE
 CLARIFY.
  
 3} THERE ARE RECEPTACLES MISSING FROM
 THE BEDROOM(#2)AND THE NEW BEDROOM.
 210.52(A).
  
 3} A RECEPTACLE PER 210.52(E) MUST BE
 INSTALLED AT THE FRONT OF THE BUILDING.
  
 4} PER 210.52(D) A RECEPTACLE IN
 COMPLIANCE WITH 210.11(C)(3) MUST BE
 INSTALLED AT BOTH SINKS IN THE NEW BATH.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved