Plan Review Notes
Plan Review Notes For Permit 05100943
Permit Number 05100943
Review Stop P
Sequence Number 1
Notes
Date Text
2005-11-16 00:00:00PAUL SCHMITZ
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 DENIED
 1) THIS PLAN ISREVIEWED UNDER 2004
 FLORIDA BUILDING CODE.
 NOTES ON PLANS SHOULD REFELECT THE SAME.
  
 2)SEC 403 MINIMUM PLUMBING FACILITIES
 TABLE 403.1 BUSINESS OUCPANCY
 ONE DRINKING FOUNTAIN REQUIRED.
 3)SHT LS.1 DETAIL "3" WATER CLOSET IS
 REQUIRED TO BE 1'6" OFF THE WALL
 4)SHT M.1 PLUMBING NOTES # 10 AIR
 CHAMBER.
 SEC 604.9 WATER HAMMER
 WATER HAMMER ARRESTORS SHALL CONFORM TO
 ASSE 1010
 5) SHT M.1 WATER ISOMETRIC
 WATER PIPE SIZE TO COMPLY WITH
 TABLE 604.3
 END OF COMMENTS QUESTIONS 561-805-6692
  
  