| Plan Review Notes For Permit 05100943 |
| Permit Number |
05100943 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-16 00:00:00 | PAUL SCHMITZ | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | DENIED | | | 1) THIS PLAN ISREVIEWED UNDER 2004 | | | FLORIDA BUILDING CODE. | | | NOTES ON PLANS SHOULD REFELECT THE SAME. | | | | | | 2)SEC 403 MINIMUM PLUMBING FACILITIES | | | TABLE 403.1 BUSINESS OUCPANCY | | | ONE DRINKING FOUNTAIN REQUIRED. | | | 3)SHT LS.1 DETAIL "3" WATER CLOSET IS | | | REQUIRED TO BE 1'6" OFF THE WALL | | | 4)SHT M.1 PLUMBING NOTES # 10 AIR | | | CHAMBER. | | | SEC 604.9 WATER HAMMER | | | WATER HAMMER ARRESTORS SHALL CONFORM TO | | | ASSE 1010 | | | 5) SHT M.1 WATER ISOMETRIC | | | WATER PIPE SIZE TO COMPLY WITH | | | TABLE 604.3 | | | END OF COMMENTS QUESTIONS 561-805-6692 | | | | | | |
|