| Plan Review Notes For Permit 05100938 |
| Permit Number |
05100938 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-09 00:00:00 | DENIED; | | | 1) FBC-2004 SEC 424.2.6.1 ENGINEERING | | | DESIGN, CONSTRUCTION AND WORKMANSHIP. | | | ANSI/NSPI-5. (ADD TO NOTES) | | | 2) FBC-2004 424.2.7.2 PUMPS AND | | | EQUIPMENT SHALL BE MOUNTED ON A | | | SUBSTANTIAL BASE IN A MANNER THAT WILL | | | ELIMINATE STRAIN ON PIPING.SLAB SHALL | | | BE A NOMINAL 4" THICK. (DETAIL) | | | 3) FBC-2004 424.2.12.1 PRESSURE TESTS. | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (ADD TO NOTES) | | | 4)424.2.9 WATER SUPPLY, LOCAL ORD. | | | #2853-95, BACKFLOW REQUIRED ON WATER | | | SERVICE. | | | 5) 424.2.14.1 JOINTS AND CONECTIONS, FBC | | | PLUMBING SEC. 605.21, PURPLE PRIMER | | | REQUIRED ON PVV PIPING. (ADD TO NOTES.) | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|