| Date |
Text |
| 2005-11-09 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT THE MANUFACTURERS |
| | SPECIFICATIONS FOR THE GEN SET AND ALL |
| | RELATED EQUIPMENT. NOTE THE TRANSFER |
| | SWITCH MUST BE SERVICE RATED PER 225.36. |
| | ALL ARTICLE 225 APPLIES TO THE |
| | GENERATOR, AS WELL AS 445, 700 & 702. |
| | |
| | 2} THE FEEDER FROM THE GENERATOR MUST BE |
| | 115% OF THE NAMEPLATE PER 445.13. |
| | |
| | 3} THE GROUNDING ELECTRODE SYSTEM MUST |
| | BE ATTACHED AT THE METER OR THE FIRST |
| | MEANS OF DISCONNECT, IT MUST BE REMOVED |
| | FROM THE ATS. THE ATS SHOULD BE BONDED |
| | WITH THE EQUIPMENT GROUNDING CONDUCTOR, |
| | UNLESS THE GENERATOR IS A SEPERATLY |
| | DERIVED SYSTEM. |
| | |
| | 4} PLEASE PROVIDE A LOAD SUMMARY FOR THE |
| | EMERGENCY LOAD. |
| | |
| | 5} THE DINING ROOM RECEPTACLES MUST |
| | COMPLY WITH 210.52(B)(1 & 2), NO OTHER |
| | OUTLETS, SEE GALLERY AND FOYER. |
| | |
| | 6}THE GFI'S IN THE MASTER BATH ARE SHOWN |
| | ON INCORRECT CIRCUITS. ONE IS SHOWN ON |
| | "C 17" (NO SUCH PANEL ON THE PLAN), THE |
| | OTHER ON "EM 7". PLEASE SEE 210.11(C(3). |
| | |
| | 7} PLEASE SEE THE CIRCUIT FOR THE FAMILY |
| | ROOMEXTENDS TO A RECEPTACLE IN THE |
| | BREAKFAST ROOM. 210.52(B). |
| | |
| | 8} PLEASE SEE BATH GFI IN THE CABANA IS |
| | INDICATED ON THE POOL PUMP CIRCUIT. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |
| | |
| | |
| | |
| | |