| 2005-12-07 00:00:00 | *** DENIED *** | | | 1) NEED ENERGY CALCULATIONS ON THE | | | ENTIRE HOUSE NOT JUST THE ADDITION ONLY. | | | 2) PLEASE CHECK THE SIZE OF THE RETURN | | | AIR GRILL ON THE FIRST FLOOR, TWO 18X12 | | | GRILLS APPEAR TO BE A 148 SQUARE INCHES | | | TO SMALL. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|