| Plan Review Notes For Permit 05100902 |
| Permit Number |
05100902 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-14 00:00:00 | DENIED: | | | | | | 1) THE CUT SHEETS AND SPEC'S NOTES UNDER | | | OPERATION STATES THAT WHEN POWER FAILS | | | THE DOORS WILL BE LOCKED AND SECURED. | | | | | | 2) THESE LOCKING DEVICES ON THE DOORS | | | MUST COMPLY WITH NFPA 101 LIFE SAFETY | | | CODE CHAPTER 7.2.1.6 SPECIAL LOCKING | | | ARRANGEMENTS. | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | | 561-804-4754 |
|