| Plan Review Notes For Permit 05100657 |
| Permit Number |
05100657 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-20 00:00:00 | *** DENIED *** | | | 1) NEED MANUAL J CALCULATIONS SHOWING | | | A/C EQUIP. SIZE REQUIRED, PER 2004 FBC/R | | | M1401.3 . | | | 2) NEED A/C SYSTEM MANUFACTURE'S NAME, | | | MODEL NUMBER, SIZE, & SEER, SHOWING ON | | | PLANS. | | | 3) SHOW LOCATION OF CONDENSER UNIT, & | | | DRAIN LINE ON PLANS. | | | 4) NEED A NOTICE OF COMMENCEMENT. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|