Plan Review Notes
Plan Review Notes For Permit 05100637
Permit Number 05100637
Review Stop E
Sequence Number 3
Notes
Date Text
2006-06-09 00:00:00****UNSAT ****
  
 ** PLEASE KNOW, ANY WORK DONE UNDER
 EARLY WORK RELEASE WAS AT CONTRACTORS
 RISK AND ANY CHANGES WILL BE THE
 RESPONSIBILTY OF THE CONTRACTORS ETC.
 PLEASE SEE NOTES BELOW AS COMMENTS WITH
 RESPECT THE 2004 FBC CHAPTER 13.
  
 PLEASE SEE THE OLD PLANS SUBMITTED BACK
 FOR REFERENCE FOR THIS PROJECT WERE FROM
 THE 1661 WORTHINGTON SITE AND OLD PLANS
 CAN NOT BE VERIFIED AT THIS TIME.
  
 1) NOTE: PLEASE SEE REQUIREMENTS FOR FBC
 CHAPTER 13 ARE REQUIRED TO BE MET FOR
 ALL LIGHTING.
 13-415.1.ABC.1.1, 13-415.1.ABC.1.2 ETC
 PLEASE CLARIFY AS SOME OF THIS IS BEING
 SHOWN, BUT UNCLEAR AS MANY LIGHTING
 CIRCUITS DO NOT INDICATE ANY CONTROL?
 PLEASE ALSO SEE THE OVER RIDE SWITCHES
 MUST STATE A MAXIMUM OF 4HRS AND A MAX
 OF 30 MINS FOR MOTION SENSORS.
 PLEASE SEE THE OVER RIDING SWITCHES
 SHALL BE LOCATED IN THE AREAS FO
 LIGHTING WHICH CAN BE SEEN BY THE
 OCCUPANT.
 PLEASE SHOW LOCATIONS OF ALL OVER RIDES
 AND OCC SENSORS.
 ** PLEASE SEE A WORST CASE SCENARIO
 SHALL BE SHOWN FOR VOLTAGE DROP PER 13-413.1.ABC.1
 **PLEASE ALSO SEE 13-415.1.ABC.1.3 FOR
 OTHER LIGHTING IN AREAS.
 ** PLEASE SEE CALCS FOR 13-415.1.AB.1
  
 2) NOTE: PLEASE SEE RISER SEEMS TO SHOW
 NEW FEEDERS FROM GUTTER TO METER ON THE
 EXISTING RISER AND THE NEW RISER SEEMS
 TO INDICATE EXISTING FEEDERS ??
 SEEMS TO BE A MISPRINT?
 215.5
  
 3) NOTE: PLEASE CLARIFY IT ROOM AND
 PLEASE SEE PART WALLS THAT DO NOT SEEM
 TO INDICATE THE 1 HR RATING ALL THE WAY
 AROUND? THIS SHOULD BE IN BUILDING
 REVIEW COMMENTS ALSO.
 PLEASE SEE NEC 645 FOR MEANS OF
 DISCONNECTS AND DETECTION SYSTEMS WHICH
 NEED TO BE SHOWN FOR THE IT ROOM.
 PLEASE INDICATE THE SHUT OFF DEVICE AND
 SHUT OFF FOR AHU.
 PLEASE INDICATE ANY RAISED FLR AND SD'S
 ABOVE AND BELOW.
 PLEASE SEE NFPA-75 , CHAPTER 6 ETC.
  
 4) NOTE: PLEASE CLARIFY EXISTING
 TRANSFORMER ON RISER AND THE LOCATION OF
 THIS TRANSFORMER. IT IS IN THE MAIN
 ELECTRICAL ROOM ? AS PLANS DO NOT SHOW.
 PLEASE SEE 450.13B, 450.21
 IF IN THE MAIN ELECTRICAL ROOM THIS
 SHOULD BE OK.
  
 5) NOTE: PLEASE SUBMIT THE SPECS ON THE
 WATT STOPPER EQUIPMENT WHICH WILL BE
 INSTALLED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCAIL PLAN REVIEW.
  
  
  