| Plan Review Notes For Permit 05100637 |
| Permit Number |
05100637 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-18 00:00:00 | PAUL SCHMITZ | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | DENIED | | | 1) SHT 963 BREAK RM SINK RM #114 | | | DOORS NOT APPROVED ON SINK BASE. | | | | | | ?11-4.24.3 KNEE CLEARANCE. KNEE | | | CLEARANCE THAT IS AT LEAST 27 IN. (685 | | | MM) HIGH, 30 IN. (760 MM) WIDE, AND 19 | | | IN (485 MM) DEEP SHALL BE | | | PROVIDED UNDERNEATH SINKS. | | | ?11-4.24.4 DEPTH. EACH SINK SHALL BE A | | | MAXIMUM OF 6-1/2 IN (165 MM) | | | DEEP. | | | ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR | | | FLOOR SPACE AT LEAST 30 IN. BY 48 | | | IN. (760 MM BY 1220 MM) COMPLYING WITH | | | 11-4.2.4 SHALL BE PROVIDED IN | | | FRONT OF A SINK TO ALLOW FORWARD | | | APPROACH.THE CLEAR FLOOR SPACE SHALL | | | BE ON AN ACCESSIBLE ROUTE AND SHALL | | | EXTEND A MAXIMUM OF 19 IN. (485 MM) | | | UNDERNEATH THE SINK (SEE FIGURE | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|