| 2006-02-08 00:00:00 | ********* UNSAT 2ND REVIEW ******** |
| | |
| | |
| | COMMERACE BANK: SUBMITTED FOR PERMIT ON |
| | JAN 23,2006 |
| | |
| | 1)NOTE: PLEASE SEE SOME NOTES FROM |
| | PREVIOUS REVIEW WHICH STILL NEED TO BE |
| | ADDRESSED. PLEASE SEE NOTES BELOW WHICH |
| | WERE TAKEN DIRECTLY FROM PREVIOUS REVIEW |
| | AND NEW NOTE FOR REPEAT COMMENTS. |
| | |
| | ** PLEASE SEE NO FORMAL RESPONSE WAS |
| | GENERATED FROM THE DESIGNER OR ONE |
| | SUBMITTED. |
| | |
| | ******** UNSAT ******** |
| | |
| | |
| | |
| | 1)NOTE: OK. |
| | |
| | 2)NOTE: OK. |
| | |
| | 3)NOTE: PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE (FAC) 61G1-16.004 |
| | WHICH REQUIRES THE PRINTED FIRM LICENSE |
| | NUMBER ON SAID TITLE BLOCK FOR |
| | ARCHITECTUAL FIRM NAME. |
| | PLEASE SEE FS 481.219 WHICH REQUIRES A |
| | "CERTIFICATE OF AUTHORIZATION"/ FIRM # |
| | NUMBER FOR SAID ARCHITECTUAL COMPANY. |
| | PLEASE SEE THE ABOVE TWO COMMENTS IS |
| | REQUIRED OF ALL SHEETS AND FOR ALL TRADE |
| | SHEETS WHETHER OR NOT COMMENTS ARE MADE |
| | BY OTHER REVIEWER(S). |
| | THIS COMMENT IS NOT FOR ENGINEERING |
| | FIRM, HOWEVER DOES AFFECT PM&E SHEETS. |
| | |
| | 4)NOTE: OK |
| | |
| | 5)NOTE:PLEASE VERIFY ALL EMERGENCY AND |
| | EXT LTS, AS THESE COULD NOT BE LOCATED |
| | ON PLANS TO MATCH UP WITH THE FIXTURE |
| | SCHEDULE AND SHOWING THESE AS CONTAINING |
| | THE MIN BATTERY BACK UP. |
| | NEW , EXISTING? |
| | PLEASE SEE NFPA-101 7.8 AND 7.9. |
| | |
| | 6)NOTE: OK. |
| | |
| | |
| | 7)NOTE: PLEASE VERIFY TAPPED CONDUCOTRS |
| | FROM MAIN GUTTER. PLEASE SEE 3/0'S ARE |
| | RATED AT 200A'S ONLY AND OCP FOR SERVICE |
| | IS SHOWN AT 210A'S. |
| | 240.4,310.16 |
| | PLEASE ALSO SEE 240.21 FOR "TAPPED" |
| | CONDUCTORS AND MIN SIZES. PLEASE SEE |
| | CONDUCTORS ARE TAPPED IN GUTTER AND THEN |
| | AGAIN IN METER, WHERE AS THE 3/0'S |
| | CONTINUE THROUGH, BUT #2'S ARE TAPPED |
| | FROM THOSE EXISITNG TAPS? |
| | PLEASE VERIFY LENGTH. |
| | ALL THIS IS SHOWN AS EXISTING, HOWEVER, |
| | PLEAS KNOW DUE TO THE EXTENT OF WORK AND |
| | POSSIBILITY OF NON-CODE COMPLIANCE, THE |
| | ABOVE WOULD NEED TO BE CORRECTED AT THIS |
| | TIME. |
| | |
| | *** NEW NOTES*** |
| | |
| | 1)NOTE: PLEASE SEE NOTE #5, NO FIXTURE |
| | LEGEND WAS SUBMITTED. |
| | |
| | 2)NOTE: PLEASE SEE PLANS WHICH WERE |
| | REDLIEND ON PREVIOUS REVIEW FOR 210.8B3 |
| | FOR KITCHENS IN OTHER THAN DWELLING |
| | UNITS FOR REQUIRED GFI PROTECTION. |
| | |
| | 3)NOTE: PLEASE SEE FLORIDA STATUES |
| | 553.80(2)(B) WITH RESPECT TO THE DESIGN |
| | PROFESSIONAL AND REPEAT COMMENTS THREE |
| | OR MORE TIMES. |
| | ** PLEASE KNOW, THIS IS ONLY A NOTICE |
| | GIVEN AT THIS TIME AND DOES NOT APPLY |
| | FOR THIS REVIEW. |
| | |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENT(S) FROM OTHER REVIEWER(S) WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD |
| | BE SUBMNITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |