| Plan Review Notes For Permit 05100637 |
| Permit Number |
05100637 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-22 00:00:00 | *** FAILED *** | | | 1) PLEASE MAKE NOTE, MATERIALS | | | EXPOSED WITHIN PLENUMS SHALL BE NON - | | | COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD | | | INDEX OF NOT MORE THAN 25 AND SMOKE - | | | DEVELOPED INDEX OF NOT MORE THAN 50 WHEN | | | TESTED IN ACCORDANCE WITH ASTM E 84. | | | | | | 2) BATHROOM EXHAUST FANS ARE SHOWING AS | | | EF-2 THERE IS NO EF-2 LISTED ON EXHAUST | | | FAN DATA. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|