Plan Review Notes
Plan Review Notes For Permit 05100637
Permit Number 05100637
Review Stop M
Sequence Number 1
Notes
Date Text
2005-12-22 00:00:00*** FAILED ***
 1) PLEASE MAKE NOTE, MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NON -
 COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND SMOKE -
 DEVELOPED INDEX OF NOT MORE THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84.
  
 2) BATHROOM EXHAUST FANS ARE SHOWING AS
 EF-2 THERE IS NO EF-2 LISTED ON EXHAUST
 FAN DATA.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.