Plan Review Notes
Plan Review Notes For Permit 05100637
Permit Number 05100637
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-11-23 00:00:00PLAN REVIEW ONLY
  
 1) DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH NFPA 241.
  
 2) THERE APPEARS TO BE NO FIRE SPRINKLER
 PROTECTION IN TELLER CASH ROOM 109.
  
 3) THE CITY OF WEST PALM BEACH FIRE
 MARSHAL OFFICE REQUIRES HVAC DUCT SMOKE
 DETECTORS TO ACTIVATE A GENERAL FIRE
 ALARM.
  
 4) THE FIRE ALARM SYSTEM IS REQUIRED TO
 BE CLASS A OR FULLY ADDRESSABLE.
  
 5) SEPARATE PERMIT APPLICATIONS AND SHOP
 DRAWINGS ARE REQUIRED FOR THE FIRE ALARM
 AND FIRE SPRINKLER SYSTEM REMODEL.
  
 6) THE INTERIOR WALLS AND CEILINGS
 FINISH MATERIAL COMPLYING WITH SECTION
 10.2 SHALL BE CLASS A OR CLASS B, IN
 EXITS AND IN EXIT ACCESS CORRIDORS. IN
 ALL OTHER AREAS, INTERIOR WALL AND
 CEILING FINISHES SHALL BE CLASS A, CLASS
 B, OR CLASS C.
  
 7) RENOVATION SHALL COMPLY WITH NFPA 101
 LIFE SAFETY CODE, 2003 EDITION.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754