| 2005-11-23 00:00:00 | PLAN REVIEW ONLY | | | | | | 1) DEMOLITION, RENOVATION, AND | | | CONSTRUCTION SHALL COMPLY WITH NFPA 241. | | | | | | 2) THERE APPEARS TO BE NO FIRE SPRINKLER | | | PROTECTION IN TELLER CASH ROOM 109. | | | | | | 3) THE CITY OF WEST PALM BEACH FIRE | | | MARSHAL OFFICE REQUIRES HVAC DUCT SMOKE | | | DETECTORS TO ACTIVATE A GENERAL FIRE | | | ALARM. | | | | | | 4) THE FIRE ALARM SYSTEM IS REQUIRED TO | | | BE CLASS A OR FULLY ADDRESSABLE. | | | | | | 5) SEPARATE PERMIT APPLICATIONS AND SHOP | | | DRAWINGS ARE REQUIRED FOR THE FIRE ALARM | | | AND FIRE SPRINKLER SYSTEM REMODEL. | | | | | | 6) THE INTERIOR WALLS AND CEILINGS | | | FINISH MATERIAL COMPLYING WITH SECTION | | | 10.2 SHALL BE CLASS A OR CLASS B, IN | | | EXITS AND IN EXIT ACCESS CORRIDORS. IN | | | ALL OTHER AREAS, INTERIOR WALL AND | | | CEILING FINISHES SHALL BE CLASS A, CLASS | | | B, OR CLASS C. | | | | | | 7) RENOVATION SHALL COMPLY WITH NFPA 101 | | | LIFE SAFETY CODE, 2003 EDITION. | | | | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | | 561-804-4754 |
|