| 2005-12-22 00:00:00 | ******** UNSAT ******** |
| | |
| | COMMERACE BANK TENAT REMODEL |
| | "PLAN REVIEW ONLY" |
| | |
| | 1)NOTE: PELASE SEE PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT |
| | BEEN SUBMITTED FOR PERMIT. |
| | |
| | 2)NOTE: PLEASE SEE FS 481.221, FAC |
| | 61G1-16.003 WHICH REQUIRES THE SEALING |
| | OF PLANS TO BE DONE WITH AN "IMPRESSION |
| | TYPE" "RAISED" SEAL. |
| | PLEASE SEE "A" SHEETS CONTAIN A "RUBBER |
| | STAMP" FOR THE ARCHITECT'S SEAL. |
| | |
| | 3)NOTE: PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE (FAC) 61G1-16.004 |
| | WHICH REQUIRES THE PRINTED FIRM LICENSE |
| | NUMBER ON SAID TITLE BLOCK FOR |
| | ARCHITECTUAL FIRM NAME. |
| | PLEASE SEE FS 481.219 WHICH REQUIRES A |
| | "CERTIFICATE OF AUTHORIZATION"/ FIRM # |
| | NUMBER FOR SAID ARCHITECTUAL COMPANY. |
| | PLEASE SEE THE ABOVE TWO COMMENTS IS |
| | REQUIRED OF ALL SHEETS AND FOR ALL TRADE |
| | SHEETS WHETHER OR NOT COMMENTS ARE MADE |
| | BY OTHER REVIEWER(S). |
| | THIS COMMENT IS NOT FOR ENGINEERING |
| | FIRM, HOWEVER DOES AFFECT PM&E SHEETS. |
| | |
| | 4)NOTE: PLEASE SEE PLANS SHOW AN ADDRESS |
| | OF 2130 CENTREPARK, HOWEVER WHEN APPLIED |
| | FOR "PLAN REVIEW" , THE PARCEL CONTROL |
| | NUMBER (PCN) USED ON APPLICATION MATCHES |
| | UP TO AN ADDRESS OF 2100 CENTREPARK , |
| | PLEASE VERIFY AND ADJUST EITHER AS |
| | NEEDED. |
| | |
| | 5)NOTE: PLEASE VERIFY ALL EMERGENCY AND |
| | EXT LTS, AS THESE COULD NOT BE LOCATED |
| | ON PLANS TO MATCH UP WITH THE FIXTURE |
| | SCHEDULE AND SHOWING THESE AS CONTAINING |
| | THE MIN BATTERY BACK UP. |
| | NEW , EXISTING? |
| | PLEASE SEE NFPA-101 7.8 AND 7.9. |
| | |
| | 6)NOTE: PLEASE SEE "A" SHEETS REFERENCE |
| | A 2004 NEC. |
| | PLEASE SEE AS OF JULY 1ST , 2003 THE |
| | STATE ADOPTED THE 2002 NEC. WE ARE |
| | CURRENTLY UNDER THAT CODE. |
| | PLEASE ALSO KNOW THE NEXT CODE THAT WILL |
| | |
| | COME INTO AFFECT FOR FUTURE KNOWLEDGE |
| | WILL BE THE 2005. |
| | |
| | 7)NOTE: PLEASE VERIFY TAPPED CONDUCOTRS |
| | FROM MAIN GUTTER. PLEASE SEE 3/0'S ARE |
| | RATED AT 200A'S ONLY AND OCP FOR SERVICE |
| | IS SHOWN AT 210A'S. |
| | 240.4,310.16 |
| | PLEASE ALSO SEE 240.21 FOR "TAPPED" |
| | CONDUCTORS AND MIN SIZES. PLEASE SEE |
| | CONDUCTORS ARE TAPPED IN GUTTER AND THEN |
| | FAIN IN METER, WHERE AS THE 3/0'S |
| | OCNTINUE THROUGH, BUT #2'S ARE TAPPED |
| | FROM THOSE EXISITNG TAPS? |
| | PLEASE VERIFY LENGTH. |
| | ALL THIS IS SHOWN AS EXISTING, HOWEVER, |
| | PLEAS KNOW DUE TO THE EXTENT OF WORK AND |
| | POSSIBILITY OF NON-CODE COMPLIANCE, THE |
| | ABOVE WOULD NEED TO BE CORRECTED AT THIS |
| | TIME. |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENT(S) FROM OTHER REVIEWER(S) WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD |
| | BE SUBMNITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |