2005-12-22 00:00:00******** UNSAT ********
  
 COMMERACE BANK TENAT REMODEL
 "PLAN REVIEW ONLY"
  
 1)NOTE: PELASE SEE PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT
 BEEN SUBMITTED FOR PERMIT.
  
 2)NOTE: PLEASE SEE FS 481.221, FAC
 61G1-16.003 WHICH REQUIRES THE SEALING
 OF PLANS TO BE DONE WITH AN "IMPRESSION
 TYPE" "RAISED" SEAL.
 PLEASE SEE "A" SHEETS CONTAIN A "RUBBER
 STAMP" FOR THE ARCHITECT'S SEAL.
  
 3)NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE (FAC) 61G1-16.004
 WHICH REQUIRES THE PRINTED FIRM LICENSE
 NUMBER ON SAID TITLE BLOCK FOR
 ARCHITECTUAL FIRM NAME.
 PLEASE SEE FS 481.219 WHICH REQUIRES A
 "CERTIFICATE OF AUTHORIZATION"/ FIRM #
 NUMBER FOR SAID ARCHITECTUAL COMPANY.
 PLEASE SEE THE ABOVE TWO COMMENTS IS
 REQUIRED OF ALL SHEETS AND FOR ALL TRADE
 SHEETS WHETHER OR NOT COMMENTS ARE MADE
 BY OTHER REVIEWER(S).
 THIS COMMENT IS NOT FOR ENGINEERING
 FIRM, HOWEVER DOES AFFECT PM&E SHEETS.
  
 4)NOTE: PLEASE SEE PLANS SHOW AN ADDRESS
 OF 2130 CENTREPARK, HOWEVER WHEN APPLIED
 FOR "PLAN REVIEW" , THE PARCEL CONTROL
 NUMBER (PCN) USED ON APPLICATION MATCHES
 UP TO AN ADDRESS OF 2100 CENTREPARK ,
 PLEASE VERIFY AND ADJUST EITHER AS
 NEEDED.
  
 5)NOTE: PLEASE VERIFY ALL EMERGENCY AND
 EXT LTS, AS THESE COULD NOT BE LOCATED
 ON PLANS TO MATCH UP WITH THE FIXTURE
 SCHEDULE AND SHOWING THESE AS CONTAINING
 THE MIN BATTERY BACK UP.
 NEW , EXISTING?
 PLEASE SEE NFPA-101 7.8 AND 7.9.
  
 6)NOTE: PLEASE SEE "A" SHEETS REFERENCE
 A 2004 NEC.
 PLEASE SEE AS OF JULY 1ST , 2003 THE
 STATE ADOPTED THE 2002 NEC. WE ARE
 CURRENTLY UNDER THAT CODE.
 PLEASE ALSO KNOW THE NEXT CODE THAT WILL
  
 COME INTO AFFECT FOR FUTURE KNOWLEDGE
 WILL BE THE 2005.
  
 7)NOTE: PLEASE VERIFY TAPPED CONDUCOTRS
 FROM MAIN GUTTER. PLEASE SEE 3/0'S ARE
 RATED AT 200A'S ONLY AND OCP FOR SERVICE
 IS SHOWN AT 210A'S.
 240.4,310.16
 PLEASE ALSO SEE 240.21 FOR "TAPPED"
 CONDUCTORS AND MIN SIZES. PLEASE SEE
 CONDUCTORS ARE TAPPED IN GUTTER AND THEN
 FAIN IN METER, WHERE AS THE 3/0'S
 OCNTINUE THROUGH, BUT #2'S ARE TAPPED
 FROM THOSE EXISITNG TAPS?
 PLEASE VERIFY LENGTH.
 ALL THIS IS SHOWN AS EXISTING, HOWEVER,
 PLEAS KNOW DUE TO THE EXTENT OF WORK AND
 POSSIBILITY OF NON-CODE COMPLIANCE, THE
 ABOVE WOULD NEED TO BE CORRECTED AT THIS
 TIME.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENT(S) FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMNITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]