| 2005-12-23 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05100637 |
| | ADD: 2100 CENTREPARK WEST |
| | CONT:PLAN REVIEW |
| | TO BE DETERMINED |
| | TEL: ()###-#### |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | ADMINISTRATIVE CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601.ALSO HEIGHT |
| | OF BUILDING. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | |
| | 3) PROVIDE INTERIOR WALL & CEILING |
| | FINISH REQUIEMENTS BY OCCUPANCY:803.5 |
| | INTERIOR FINISH REQUIREMENTS BASED ON |
| | GROUP. |
| | INTERIOR WALL AND CEILING FINISH SHALL |
| | HAVE A FLAME SPREAD INDEX NOT GREATER |
| | THAN THAT SPECIFIED IN TABLE 803.5 FOR |
| | THE GROUP AND LOCATION DESIGNATED. |
| | INTERIOR WALL AND CEILING FINISH |
| | MATERIALS, OTHER THAN TEXTILES, TESTED |
| | IN ACCORDANCE WITH NFPA 286 AND MEETING |
| | THE ACCEPTANCE CRITERIA OF SECTION |
| | 803.2.1 , SHALL BE PERMITTED TO BE USED |
| | WHERE A CLASS A CLASSIFICATION IN |
| | ACCORDANCE WITH ASTM E 84 IS REQUIRED. |
| | |
| | 4) (2004 FBC) 106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND REVELENT |
| | LAWS, ORDINANCES, AND RULES AND |
| | REGULATIONS AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | SHEET A201 INDICATES A STAIR TOWER |
| | HEIGHT OF BUILDING UNKOWN, THE STAIR |
| | TOWER IS UNIDENTIFIABLE EXCEPT FOR DOOR# |
| | 123. IN THIS STAIR TOWER THERE IS A |
| | OPENING BLOCKED BUT NO DETAIL GIVING THE |
| | |
| | UL LISTING AND FIRE RESISTANCE RATING. |
| | |
| | 5) A202 INDICATES DOOR# 119 MISSING 18" |
| | LATCH SIDE OF DOOR,SEE,11-4.13.6 |
| | MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| | MANEUVERING CLEARENCES AT DOORS THAT ARE |
| | NOT AUTOMATIC OR POWER-ASSISTED SHALL BE |
| | AS SHOWN IN FIG. 25. THE FLOOR OR GROUND |
| | AREA WITH IN THE REQUIRED CLEARENCES |
| | SHALL BE CLEAR & LEVEL. |
| | |
| | 6)-910 PLANS INDICATE DROPPED CEINGS OR |
| | SOFFITS WITH THE USE OF FRAMING HUNG |
| | FROM THE STRUCTURE ABOVE. PROVIDE WHAT |
| | TYPE OF MATERIAL THIS IS AND HOW OFTEN |
| | THE FRAMING IS TO BE ATTACHED, AND BY |
| | WHAT METHOD. |
| | |
| | 7) A963 INDICATES (2) KITCHEN UNITS BUT |
| | NO INFORMATION AS TO: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARENCE THAT IS AT |
| | LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| | SHALL BE PROVIDED UNDERNEATH SINKS. |
| | |
| | 8) RESTROOMS:1210.2 WALLS. |
| | WALLS WITHIN 2 FEET (610 MM) OF URINALS |
| | AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT |
| | OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND |
| | EXCEPT FOR STRUCTURAL ELEMENTS, THE |
| | MATERIALS USED IN SUCH WALLS SHALL BE OF |
| | A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE. |
| | |
| | 9)PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | (RAISED)TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | BUILDING PLAN REVIEW |