Plan Review Notes
Plan Review Notes For Permit 05100635
Permit Number 05100635
Review Stop M
Sequence Number 6
Notes
Date Text
2006-08-11 00:00:00CALLED ENGINEER (BOB FORMICA),
 ARCHITECTURAL PLANS WERE REVISED TO
 WHICH NOW THE MECHANICAL PLANS ARE NO
 LONGER CODE COMPLIANT.DUCTS
 PENETRATING FIRE RATED WALLS OR
 PARTITIONS SHALL BE PROTECTED BY FIRE
 DAMPERS 2004 FMC 607.5.3.
  
 FLEX DUCTS ARE NOT PERMITTED TO
 PENETRATE RATED WALLS OR PARTITIONS PER
 2004 FMC 607.7
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  