| 2006-07-27 00:00:00 | ***UNSAT *** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW. |
| | |
| | ** PLEASE KNOW ANY "EARLY WORK RELEASE" |
| | GRANTED BY THE BUILDING OFFICAL WAS AT |
| | CONTRACTOR'S OWN RISK. |
| | |
| | |
| | 1 NOTE: PLEASE SEE REQUIREMENTS FOR |
| | FBC CHAPTER 13 ARE REQUIRED TO BE MET |
| | FOR ALL LIGHTING. |
| | 13-415.1.ABC.1.1, 13-415.1.ABC.1.2 ETC |
| | PLEASE SEE THE OVER RIDE SWITCHES |
| | MUST STATE A MAXIMUM OF 4HRS AND A MAX |
| | OF 30 MINS FOR MOTION SENSORS FOR |
| | DEVICES AND LOCATIONS. |
| | PLEASE SEE WORST CASE VD COULD NOT BE |
| | LOCATED FOR ANY ONE BRANCH CIRCUIT. OR |
| | FEEDER? 13-413 |
| | PLEASE KNOW, A "SWITCH" IS NOT A DEVICE |
| | FOR CONTROL. IT MUST BE PART OF THE |
| | SYSTEM AND SHALL HAVE LIMITS TO TIME |
| | ETC. PLEASE BE SURE TO LIST THE TIMES |
| | FOR MAX OVER RIDE. |
| | ** PLEASE SEE CALCS FOR 13-415.1.AB.1, |
| | 13-415.2.ABC.1, TABLES 415.2.C.1, |
| | 415.2.B.1. |
| | PLEASE SEE CALCULATIONS SUBMITTED ARE |
| | THE SAME ONES FROM 2/27/06 AND HAVE NOT |
| | BEEN REVISED TO INCLUDE LIGHITNG DESIGN |
| | (DESIGN WATTAGE) DESIGN MAX ALLOWANCE( |
| | PERMITTED LPD'S PER TABLES) ETC., |
| | PLEASE ALSO SEE IT WAS NOTED ON PREVIOUS |
| | REVIEW FROM THE MECHANICAL REVIEWER THAT |
| | THE CALCULATIONS WERE SEALED |
| | "PHOTO-COPIES" OF SIGNED DOCUMENTS. |
| | PLEASE SEE FS 471.025, FBC CHAPTER 13 AS |
| | THESE ARE REQUIRED TO CONTAIN THE |
| | "ORIGINAL" SIGNATURE , DATE AND RAISED |
| | SEAL FOR THE DESIGNER OF RECORD. MAY NOT |
| | PLACE A "RAISED SEAL" OVER PHOTO-COPIED |
| | SIGNATURES. |
| | |
| | PLACED TWO PHONE CALLS TO CONTRACTOR ETC |
| | WITH RESPECT TO CALCULATIONS. |
| | |
| | 2) NOTE: PLEASE COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | PLEASE SEE THAT ALL OLD/VOIDED SHEETS |
| | WERE LEFT IN SETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW.ONCE AGAIN IF THERE ARE ANY |
| | QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |