| 2006-06-09 00:00:00 | ***UNSAT *** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEWS AND NOTES PER NEW FBC 2004 |
| | CHAPTER 13. |
| | |
| | ** PLEASE KNOW, EARLY WORK RELEASE WHICH |
| | WAS GRANTED BY THE BUILDING OFFICIAL WAS |
| | AT OWNER/CONTRACTORS OWN RISK. |
| | |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTE WITH |
| | RESPECT TONEC 645, NFPA-75. |
| | PLEASE SEE MEANS OF SHUTTING DOWN ALL |
| | ELECTRICAL, A/C SYSTEMS AND SEPARATIONS |
| | COULD NOT BE LOCATED ON PLANS. |
| | 645.1-645.16 NFPA-75 PLEASE SEE ALL |
| | CHAPTERS |
| | ** PLEASE SEE THIS REVIEW COMMENT HAS |
| | BEEN REPEATED THREE TIMES AND A NOTICE |
| | TO FS 553.80(2)(B) WAS GIVEN ON THE |
| | PREVIOUS REVIEWS WITH RESPECT TO REPEAT |
| | COMMENTS THREE OR MORE TIMES. PLEASE |
| | KNOW AS THE FIRST TWO REVIEWS WERE "PLAN |
| | REVIEW"ONLY, IF THIS COMMENT IS NOT |
| | ADDRESSED ON THE FOLLOWING REVIEW A 4X |
| | PLAN REVIEW FEE WILL BE ASSESSED. |
| | |
| | 21) NOTE: PLEASE SEE REQUIREMENTS FOR |
| | FBC CHAPTER 13 ARE REQUIRED TO BE MET |
| | FOR ALL LIGHTING. |
| | 13-415.1.ABC.1.1, 13-415.1.ABC.1.2 ETC |
| | PLEASE CLARIFY AS SOME OF THIS IS BEING |
| | SHOWN, BUT UNCLEAR AS MANY LIGHTING |
| | CIRCUITS DO NOT INDICATE ANY CONTROL? |
| | PLEASE ALSO SEE THE OVER RIDE SWITCHES |
| | MUST STATE A MAXIMUM OF 4HRS AND A MAX |
| | OF 30 MINS FOR MOTION SENSORS. |
| | PLEASE SEE THE OVER RIDING SWITCHES |
| | SHALL BE LOCATED IN THE AREAS FOR |
| | LIGHTING WHICH CAN BE SEEN BY THE |
| | OCCUPANT. A NOTE ON THE PLAN MENTIONS AN |
| | OVER RIDE SWITCH IN THE ELECTRICAL |
| | CLOSET WHICH WILL NOT BE ACCEPTED. |
| | PLEASE SHOW LOCATIONS OF ALL OVER RIDES |
| | AND OCC SENSORS. |
| | ** PLEASE SEE A WORST CASE SCENARIO |
| | SHALL BE SHOWN FOR VOLTAGE DROP PER |
| | 13-413.1.ABC.1 |
| | **PLEASE ALSO SEE 13-415.1.ABC.1.3 FOR |
| | OTHER LIGHTING INSEPARATE SPACES |
| | /ROOMS AREAS. |
| | PLEASE KNOW, A "SWITCH" IS NOT A DEVICE |
| | FOR CONTROL. IT MUST BE PART OF THE |
| | SYSTEM AND SHALL HAVE LIMITS TO TIME |
| | ETC. |
| | ** PLEASE SEE CALCS FOR 13-415.1.AB.1 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |