| 2006-02-08 00:00:00 | ********* UNSAT 2ND REVIEW ******* |
| | |
| | 1)NOTE: PLEASE SEE ALMOST ALL COMMENTS |
| | FROM PREVIOUS REVIEW STILL APPLY. |
| | PLEASE SEE IT SEEMS ONLY COMMENTS #1 AND |
| | #3 WERE ADDRESSED. |
| | |
| | ** PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. PLEASE |
| | ALSO SEE ONE NEW NOTE WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | |
| | |
| | ******** UNSAT ********* |
| | |
| | |
| | |
| | |
| | 1)NOTE: OK |
| | |
| | |
| | ************************************* |
| | 2)NOTE: PLEASE SEE MISSING LICENSE |
| | INFORMATION REQUIRED FOR ARCHITECTUAL |
| | FIRM ON TITLE BLOCKS. |
| | PLEASE SEEFLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.004 AND FS 481.219. |
| | PLEASE KNOW, THIS IS REQUIRED FOR ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | *************************************** |
| | 3)NOTE: OK |
| | |
| | |
| | |
| | |
| | |
| | *************************************** |
| | |
| | 4)NOTE: PLEASE SEE 645.2,645.10,645.15 |
| | ETC FOR MISSING REQUIRED INFORMATION FOR |
| | "IT" ROOM. |
| | PLEASE SEE ELECTRICAL REQUIREMENTS PER |
| | NFPA-70 AND NFPA-75 |
| | |
| | PLEASEALSO SEEMISSING FIRE RATING OF |
| | RM, FIRE/SMOKE DAMPERS ETC REQUIRED. |
| | |
| | 5)NOTE: PLEASE SEE PLANS INCLUDING |
| | A-SHEETS REFERENCE A 2004 ELECTRICAL |
| | CODE. |
| | PLEASE SEE AS OF JULY 1ST,2003 WE ARE |
| | UNDER THE 2002 NEC. |
| | **NOTE, THE NEXT ELECTRICAL CODE WILL BE |
| | THE 2005 NOT YET ADOPTED BY THE STATE. |
| | |
| | 6)NOTE: PLEASE PROVIDE LOAD CALCULATIONS |
| | FOR NEW ADDED LOADS TO EXISTING SERVICE. |
| | NONE SUBMITTED. |
| | 220,220.3,220.10,220.11,220.13, ETC |
| | CONTINUOUS LOADS 215.3, 230.42 |
| | |
| | 7)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS |
| | IN OTHER THAN DWELLING UNITS. |
| | |
| | *************************************** |
| | NEW NOTE: |
| | |
| | 1)NOTE: PLEASE SEE COPY OF FLORIDA |
| | STATUES 553.80(2)(3) WITH RESPECT TO |
| | DESIGN PROFESSIONALS AND REPEAT COMMENTS |
| | THREE OR MORE TIMES. PLEASE BE SURE ALL |
| | COMMENTS ARE ADDRESSED. |
| | |
| | |
| | 2)NOTE: PLEASE COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. |
| | PLEASE BE SURE TO SUBMIT ONE COPY OF |
| | OLD/VOIDED SHEETS FOR REFERENCE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |