Plan Review Notes
Plan Review Notes For Permit 05100635
Permit Number 05100635
Review Stop E
Sequence Number 3
Notes
Date Text
2006-02-08 00:00:00********* UNSAT 2ND REVIEW *******
  
 1)NOTE: PLEASE SEE ALMOST ALL COMMENTS
 FROM PREVIOUS REVIEW STILL APPLY.
 PLEASE SEE IT SEEMS ONLY COMMENTS #1 AND
 #3 WERE ADDRESSED.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW. PLEASE
 ALSO SEE ONE NEW NOTE WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
  
  
 ******** UNSAT *********
  
  
  
  
 1)NOTE: OK
  
  
 *************************************
 2)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED FOR ARCHITECTUAL
 FIRM ON TITLE BLOCKS.
 PLEASE SEEFLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FS 481.219.
 PLEASE KNOW, THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 ***************************************
 3)NOTE: OK
  
  
  
  
  
 ***************************************
  
 4)NOTE: PLEASE SEE 645.2,645.10,645.15
 ETC FOR MISSING REQUIRED INFORMATION FOR
 "IT" ROOM.
 PLEASE SEE ELECTRICAL REQUIREMENTS PER
 NFPA-70 AND NFPA-75
  
 PLEASEALSO SEEMISSING FIRE RATING OF
 RM, FIRE/SMOKE DAMPERS ETC REQUIRED.
  
 5)NOTE: PLEASE SEE PLANS INCLUDING
 A-SHEETS REFERENCE A 2004 ELECTRICAL
 CODE.
 PLEASE SEE AS OF JULY 1ST,2003 WE ARE
 UNDER THE 2002 NEC.
 **NOTE, THE NEXT ELECTRICAL CODE WILL BE
 THE 2005 NOT YET ADOPTED BY THE STATE.
  
 6)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 FOR NEW ADDED LOADS TO EXISTING SERVICE.
 NONE SUBMITTED.
 220,220.3,220.10,220.11,220.13, ETC
 CONTINUOUS LOADS 215.3, 230.42
  
 7)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS
 IN OTHER THAN DWELLING UNITS.
  
 ***************************************
 NEW NOTE:
  
 1)NOTE: PLEASE SEE COPY OF FLORIDA
 STATUES 553.80(2)(3) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS
 THREE OR MORE TIMES. PLEASE BE SURE ALL
 COMMENTS ARE ADDRESSED.
  
  
 2)NOTE: PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 PLEASE BE SURE TO SUBMIT ONE COPY OF
 OLD/VOIDED SHEETS FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]