| 2006-01-03 00:00:00 | ******** UNSAT ********* |
| | |
| | |
| | ** PLANS ONLY SUBMITTED FOR "PLAN |
| | REVIEW" AND NOT FOR PERMIT. |
| | |
| | 1)NOTE: PLEASE SUBMIT COMPLETE ATTACHED |
| | SETS FOR REVIEW AND STAMPING. |
| | PLEASE SEE EACH SET CONTAINS ALL LOSE |
| | SHEETS AND NOTHING IS ATTACHED. |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM |
| | SETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO COMPLETED SETS. |
| | ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| | SEPARATE FOR REFERENCE. |
| | |
| | |
| | ************************************* |
| | 2)NOTE: PLEASE SEE MISSING LICENSE |
| | INFORMATION REQUIRED FOR ARCHITECTUAL |
| | FIRM ON TITLE BLOCKS. |
| | PLEASE SEEFLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.004 AND FS 481.219. |
| | PLEASE KNOW, THIS IS REQUIRED FOR ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | *************************************** |
| | 3)NOTE: PLEASE SEE MANY ARCHITECTUAL |
| | SHEETS CONTAIN A "RUBBER STAMP" FOR THE |
| | ARCHITECT'S REQUIRED "RAISED/IMPRESSION" |
| | TYPE SEAL. |
| | PLEASE SEE FS 481.221 |
| | THIS IS REQUIRED OF ALL SHEETS. PLEASE |
| | SEE SOME SHEETS DO CONTAIN THE REQUIRED |
| | "RAISED SEAL". |
| | *************************************** |
| | |
| | 4)NOTE: PLEASE SEE 645.2,645.10,645.15 |
| | ETC FOR MISSING REQUIRED INFORMATION FOR |
| | "IT" ROOM. |
| | PLEASE SEE ELECTRICAL REQUIREMENTS PER |
| | NFPA-70 AND NFPA-75 |
| | |
| | PLEASEALSO SEEMISSING FIRE RATING OF |
| | RM, FIRE/SMOKE DAMPERS ETC REQUIRED. |
| | |
| | 5)NOTE: PLEASE SEE PLANS INCLUDING |
| | A-SHEETS REFERENCE A 2004 ELECTRICAL |
| | CODE. |
| | PLEASE SEE AS OF JULY 1ST,2003 WE ARE |
| | UNDER THE 2002 NEC. |
| | **NOTE, THE NEXT ELECTRICAL CODE WILL BE |
| | THE 2005 NOT YET ADOPTED BY THE STATE. |
| | |
| | 6)NOTE: PLEASE PROVIDE LOAD CALCULATIONS |
| | FOR NEW ADDED LOADS TO EXISTING SERVICE. |
| | NONE SUBMITTED. |
| | 220,220.3,220.10,220.11,220.13, ETC |
| | CONTINUOUS LOADS 215.3, 230.42 |
| | |
| | 7)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS |
| | IN OTHER THAN DWELLING UNITS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |