| Plan Review Notes For Permit 05100635 |
| Permit Number |
05100635 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-01-19 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05100635 | | | ADD: 1661 WORTHINGTON RD | | | CONT: "PLAN REVIEW" | | | TEL: (954)689-6905 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1) 106.1.2 ADDITIONAL DATA. THE BUILDING | | | OFFICIAL MAY REQUIRE ALL DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | REQUIRED BY THE BUILDING OFFICIAL TO BE | | | ASSEMBLED INTO PERMIT READY SETS OF | | | PLANS. PLANS ARE LOOSE AND UNORGANIZED. | | | | | | 2)SEE THE VARIOUS REVIEWERS COMMENTS ON: | | | 2A) ORIGINAL PLANS STILL HAVE RUBBER | | | STAMP SEAL, NOT THE REQUIRED RAISED | | | EMBOSSED SEAL. | | | 2B) FL ADMINISTRATIVE CODE 481.219 | | | REQUIRES THE ARCHITECTURAL FIRM TO HAVE | | | THEIR CERTIFICATE OF AUTHORIZATION | | | NUMBER IN TITLEBLOCK. | | | | | | 3)COMMENT# 3 FROM THE PREVIOUS REVIEW | | | DELT WITH NO INFORMATION ON THE KITHEN | | | CABINETS AND SINK. | | | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | | BE MOUNTED WITH THE COUNTER NO HIGHER | | | THAN 34" ABOVE THE FINISH FLOOR. | | | 11-4.24.3 KNEE CLEARENCE THAT IS AT | | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | | SHALL BE PROVIDED UNDERNEATH SINKS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|