2006-01-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05100635
 ADD: 1661 WORTHINGTON RD
 CONT: "PLAN REVIEW"
 TEL: (954)689-6905
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) 106.1.2 ADDITIONAL DATA. THE BUILDING
 OFFICIAL MAY REQUIRE ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 ASSEMBLED INTO PERMIT READY SETS OF
 PLANS. PLANS ARE LOOSE AND UNORGANIZED.
  
 2)SEE THE VARIOUS REVIEWERS COMMENTS ON:
 2A) ORIGINAL PLANS STILL HAVE RUBBER
 STAMP SEAL, NOT THE REQUIRED RAISED
 EMBOSSED SEAL.
 2B) FL ADMINISTRATIVE CODE 481.219
 REQUIRES THE ARCHITECTURAL FIRM TO HAVE
 THEIR CERTIFICATE OF AUTHORIZATION
 NUMBER IN TITLEBLOCK.
  
 3)COMMENT# 3 FROM THE PREVIOUS REVIEW
 DELT WITH NO INFORMATION ON THE KITHEN
 CABINETS AND SINK.
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026