Plan Review Notes
Plan Review Notes For Permit 05100635
Permit Number 05100635
Review Stop P
Sequence Number 1
Notes
Date Text
2005-11-17 00:00:00PAUL SCHMITZ
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 DENIED
 1)SHT P1.01 A/C CONDENSATE DISPOSAL:
 OPTIONS RTU TO ROOF DRAINS.
 IF BELOW ROOF TERMINATE TO STORM
 OUTSIDE OF BUILDING,
 PLANTER OR DRY WELL.
 2)SHT P2.01 DETAIL WATER HEATER:
 SEC 607.3 PROVIDE INFORMATION FOR
 THERMAL EXPASNSION CONTROL.
 3)SHT P2.01 WATER RISER:
 EXPLAIN ABBREVIATION WATTS BRVT.
 SHOW ON PLUMBING LEGEND.
 4) SEC 403 MINIMUM REQUIRED NUMBER OF
 PLUMBING FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDEDFOR
 THE TYPE OF OCCUPANCY AND THE MINIMUM
 NUMBER SHOWN IN TABLE 403.1
 SEC 410 DRINKING FOUNTAINS.1-PER 100
 END OF COMMENTS QUESTIONS 561-805-6692