| 2005-11-17 00:00:00 | PAUL SCHMITZ | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | DENIED | | | 1)SHT P1.01 A/C CONDENSATE DISPOSAL: | | | OPTIONS RTU TO ROOF DRAINS. | | | IF BELOW ROOF TERMINATE TO STORM | | | OUTSIDE OF BUILDING, | | | PLANTER OR DRY WELL. | | | 2)SHT P2.01 DETAIL WATER HEATER: | | | SEC 607.3 PROVIDE INFORMATION FOR | | | THERMAL EXPASNSION CONTROL. | | | 3)SHT P2.01 WATER RISER: | | | EXPLAIN ABBREVIATION WATTS BRVT. | | | SHOW ON PLUMBING LEGEND. | | | 4) SEC 403 MINIMUM REQUIRED NUMBER OF | | | PLUMBING FIXTURES. | | | PLUMBING FIXTURES SHALL BE PROVIDEDFOR | | | THE TYPE OF OCCUPANCY AND THE MINIMUM | | | NUMBER SHOWN IN TABLE 403.1 | | | SEC 410 DRINKING FOUNTAINS.1-PER 100 | | | END OF COMMENTS QUESTIONS 561-805-6692 |
|