| Plan Review Notes For Permit 05100635 |
| Permit Number |
05100635 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-21 00:00:00 | ----------------PROVISO----------------- | | | | | | 1.NO ROOF PLAN PROVIDED. ENSURE THAT | | | THERE | | | ARE NO PLUMBING VENTS OR EXHAUST OUTLETS | | | WITHIN 10 FEET OF RTU OUTSIDE AIR | | | INTAKES. | | | | | | 2.MECHANICAL PLAN SHOWS EF 2 (SEE FAN | | | SCHEDULE) IN GANG BATHROOMS AND EF 1 IN | | | CLOSET.ELECTRICAL PLAN CALLS FOR THE | | | REVERSE.EF 2 IS THE CORRECT FAN FOR | | | THE GANG BATHROOMS. | | | | | | ANY QUESTIONS PLEASE CALL RONALD J | | | REGUEIRO AT 561-805-6734 OR | | | [email protected] |
|