| Plan Review Notes For Permit 05100635 |
| Permit Number |
05100635 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-16 00:00:00 | ******DENIED****** | | | | | | 1) EACH SHEET OF THE DRAWINGS ARE TO BE | | | SIGNED, DATED AND SEALED IN ACCORDANCE | | | WITH FS REQUIREMENTS. | | | | | | 2) LIFE SAFETY TO COMPLY WITH NFPA-101, | | | AND NFPA-1, 2003 EDITIONS. | | | | | | 3) PLEASE INDICATE THE INTERIOR FINISH | | | CLASSIFICATION OF WALLS AND CEILING IN | | | TERMS OF CLASS A, B OR C. | | | | | | 4) IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM, NOT | | | SUPERVISORY SIGNAL WHEN ACTIVATED. | | | | | | 5) IN ADDITION TO THE FIRE SPRINKLER | | | SYSTEM, SEPARATE SHOP DRAWINGS AND | | | PERMITS ARE REQUIRED FOR FIRE ALARM | | | REMODEL. | | | | | | 6) PLEASE NOTE THE LOCATIONS OF REQUIRED | | | 2A-10B,C RATED FIRE EXTINGUISHERS, THAT | | | SHALL NOT EXCEED 75' TRAVEL DISTANCE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|