2005-11-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05100635
 ADD: 1661 WORTHINGTON RD
 CONT: "PLAN REVIEW"
 TEL: (954)689-6905
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS DO NOT INDICATE AS TO WHAT CODE
 THEY WERE DESIGNED TOO?SEE 110.2
 INFORMATION REQUIRED FOR CERTIFICATE OF
 OCCUPANCY, SEE 12 ITEMS THAT WILL BE
 REQUIRED FOR PERMIT ISSUANCE AND C.O.
  
 2)SHEET A-200 FLOOR PLAN HAS VARIOUS
 DOORS THAT DOESN'T COMPLY WITH THE
 MANEUVERING CLEARENCES AT DOORWAYS.
 SEE THE REQUIRED 18" AT THE LATCH ON THE
 PULL SIDE OF THE DOOR.
 11-4.13.6 MANEUVERING CLEARANCES AT
 DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIGURE 11-25.THE FLOOR OR
 GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR.
 DOORS 106, 107,108,KITCHEN CLOSET DOOR
 109, 114B, 115 & 119.
  
 3) KITCHEN(109) PROVIDE ELEVATIONS OF
 COUNTER W/ SINK, COMPLY WITH:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 4)PROVIDE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION.TABLE 803.5
 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR
 FINISH REQUIREMENTS BASED ON OCCUPANCY.
  
 5) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,VARIOUS
 SHEETS INDICATE DIFFERENT TYPES OF
 STRUCTURAL COMPONENTS ABOVE THE FINISH
 CEILING A003 INDICATES DECK WITH NO TYPE
 DECLARED, A9.10 INDICATES A CONCRETE
 DECK AND P2.01 INDICATES BAR JOIST.
 SHEET A-400 INDICATES VARIOUS DROPPED
 DRYWALL CEILINGS BUT NO MENTION AS TO
 TYPE OF DECK ABOVE, TYPE OF FASTENER,
 SPACING OF FRAMING, TYPE OF FRAMING,
 IF STIFF BACKS ARE REQUIRED NOR THE
 THICKNESSS OF DRYWALL?
  
 6)A006 WALL FINISH SCHEDULE DOESN'T
 INDICATE EALL FINISH IN RESTROOMS, SEE
 REQUIREMENTS 1210.2 FOR A SMOOTH,HARD
 AND NONABSORBANT SURFACE TO A HEIGHT OF
 4'-0" AT WATERCLOSETS & URINALS.
  
 7) CORRECT ENERGY FORM TO THE FORM 400A
 2004 EDITION.
  
 8) LETTER OF AUTHORIZATION FROM BANK
 INDICATES EXTERIOR MODIFICATIONS?
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW