| Plan Review Notes For Permit 05100510 |
| Permit Number |
05100510 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-17 00:00:00 | ********* UNSAT ******* | | | | | | 1)NOTE: PLEASE VERIFY LOADS/LAOD | | | CALCUALTIONS FOR TRACK LIGHTING, SHOW | | | WINDOWS PER 220.12A&B | | | | | | 2)NOTE: LOAD CALCULATIONS COULD NOT BE | | | LOCATED. | | | PLEASE VERIFY ALL CONTINUOUS @ 125%, | | | 215.3,230.42 ETC. | | | | | | 3)NOTE: PLEASE SEE TRANSFORMER DOES | | | INDICATE GROUNDINF ELECTRODE FOR | | | SEPARTELY DERIVED SYSTEM TO BLDG STEEL | | | AND CWP, HOWEVER PLEASE INDICATE TO MAIN | | | GE SYSTEM. | | | 250.30 | | | PLEASE ALSO INDICATE THE "EQUIPMENT | | | GROUNDING CONDUCTOR FROM PANEL "H" TO | | | TRANSFORMER. | | | 250.30,250.110,,,, | | | ONLY THE NEUTRAL IS NOT BROUGHT TO THE | | | TRANSFORMER. | | | | | | 4)NOTE: PLEASE SUBMIT THE AIC RATINGS | | | FOR THE NEW ELECTRICAL SERVICE | | | EQUIPMENT. | | | 110.9,215.5 | | | | | | 5)NOTE: PLEASE VERIFY MIN OCP FOR AHU'S | | | CONTAINING HEAT , SHALL BE BASED ON MIN | | | OCP AT 125% PER 424.3B | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** PLEASE REMOVE ANY OLD/VOIDED SHEETS | | | AND ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETSFOR REVIEW AND STAMPING. | | | PLEASE SUBMIT ONE SET OF OLD SHEETS FOR | | | REFERENCE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|