| Plan Review Notes For Permit 05100475 |
| Permit Number |
05100475 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-09 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SHOW LOCATIONS OF EXIT LIGHTS | | | AND EMERGENCY LIGHTING FACILITIES NEW OR | | | EXISTING. | | | | | | 2) 2A-10 B,C RATED FIRE EXTINGUISHERS | | | ARE REQUIRED TO BE MOUNTED NOT TO EXCEED | | | 75' TRAVEL DISTANCE. | | | | | | 3) IS THERE AN EXISTING FIRE SPRINKLER/ | | | FIRE ALARM SYSTEM? IF SO, SYSTEMS SHALL | | | BE MAINTAINED AND OPERABLE DURING | | | RENOVATION. | | | | | | 4) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|