2005-11-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05100475
 ADD: 325 CLEMATIS ST. SUITE A
 CONT: DENNIS PETERSON
 TEL: (561)622-8290
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE SYMBOLS FOR NEW WALLS IS NOT USED
 ON SHEET A04 OR A05. IT IS DIFFICULT TO
 TELL WHAT WILL BE EXISTING AND WHAT IS
 NEW?
  
 2) THE DOOR TO THE REAR STAIRWWELL
 APPEARS TO ALSO HAVE BEEN MOVED WITHOUT
 SYMBOLS INDICATING SUCH. SEE A01 VS A05.
 IN ITHER CASE THE DEFINITION OF EXIT:
 EXIT. THAT PORTION OF THE MEANS OF
 EGRESS WHICH IS SEPARATED FROM ALL
 OTHER SPACES OF A BUILDING OR STRUCTURE
 BY CONSTRUCTION AND OPENING
 PROTECTIVES, AS REQUIRED FOR EXITS, TO
 PROVIDE A PROTECTED WAY OF TRAVEL
 TO THE EXIT DISCHARGE. EXITS INCLUDE
 EXTERIOR EXIT DOORS, SEPARATED EXIT
 STAIRS, EXIT PASSAGEWAYS AND HORIZONTAL
 EXITS.
 THE BREAK ROOM SHOULD NOT HAVE A DOOR
 DIRECTLY INTO THE EXIT. NOR SHOULD THE
 MENS RESTROOM HAVE A DOOR DIRECTLY IN
 THE EXIT.ALSO SEE 1006.1.1.
  
 3) THE CORRIDOR TO THE BREAK ROOM IS TO
 NARROW, A MINIMUM OF 36" SHALL BE
 REQUIRED, SEE TABLE 1004 FOOTNOTE 10.
  
 4) THE PLANS DO NOT INDICATE WORK IN THE
 COMMON AREAS BUT TO CORRECT THE DOORWAYS
 INTO THE STAIRWELL THIS ENVOKES THE
 11-4.1.6 ACCESSIBLE BUILDINGS
 ALTERATIONS,EGRESS IN THE COMMON AREAS
 UNDER ALTERATIONS. INDICATE WHERE THE
 REQUIRED (2) AREA OF RESCUE ASSISTANCE
 SHALL BE PROVIDE 11-4.1.3(9). SEE
 11-4.3.11 FOR LOCATION & CONSTRUCTION.
  
 5)FL BLDCODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANAS DO NOT PROVIDE AN ELEVATION OF
 THE BREAKROOM SINK SEE:
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED
 WITH THE COUNTER OR RIM NO HIGHER THAN
 34 IN. (865 MM) ABOVE THE FINISH FLOOR.
  
 11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
  
 11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
  
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
  
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
  
 11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  