| Plan Review Notes For Permit 05100453 |
| Permit Number |
05100453 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-17 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | | EXISTING LOADS AND THE EXISTING OR | | | PROPOSED SERVICE SPECIFICATIONS PER | | | 215.15. | | | | | | 2} THE PLAN INDICATES THE SUB PANEL IS | | | FED FROM A SEPERATE BUILDING. THE | | | SUBPANEL MUST BE GROUNDED PER 250.32, | | | AND HAVE A MAIN BREAKER, OR A SEPERATE | | | DISCONNECTING MEANS AT THE BUILDING | | | SERVED PER 225.31. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|