| Plan Review Notes For Permit 05100446 |
| Permit Number |
05100446 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-21 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE GROUND WIRE SHOWN FROM THE METER | | | TO THE ATS' PARALLELS THE NEUTRAL AND | | | CANNOT BE INSTALLED. ALSO NOTE THAT THE | | | ATS' BECOME THE FIRST MEANS OF | | | DISCONNECT AND THE NEUTRAL MUST BE | | | ISOLATED AT THAT POINT. | | | | | | 2} INDICATE THE TYPE OF FUEL, NATURAL OR | | | LP GAS. THIS CAN BE HIGHLIGHTED ON THE | | | SPEC SHEET. | | | | | | 3} PLEASE SHOW THE LOCATION OF ALL THE | | | SERVICE EQUIPMENT ON THE SITE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|