| Plan Review Notes For Permit 05100397 |
| Permit Number |
05100397 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-10-18 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- POLYSTICK CAN NOT BE USED FOR ROOF | | | TILE UNDERLAYMENT. SEE LIMITATION #2 ON | | | DADE COUNTY NOA SUBMITTED. | | | UNDERLAYMENT MUST BE MECHANICALLY | | | ATTACHED TO THE DECK. | | | | | | 2- POLYFOAM PRODUCT APPROVAL: PROVIDE | | | COPIES OF THE SAME REPORT THAT WAS | | | SUBMITTED FOR FLORIDA PRODUCT APPROVAL. | | | THERE IS NO DADE COUNTY NOA REPORT | | | SUBMITTED FOR FLORIDA APPROVAL. SEE | | | WWW.FLORIDABUILDING.ORG AND DOWNLOAD THE | | | REPORTS SUBMITTED FOR APPROVAL. | | | | | | 3- CLAY TILE: NEED THE CURRENT FLORIDA | | | PRODUCT APPROVAL. PRODUCT APPROVAL | | | SUBMITTED WAS FOR FBC 2001. NEED THE FBC | | | 2004 APPROVED PRODUCT. GO TO THE WEBSITE | | | WWW.FLORIDABUILDING.ORG TO DOWNLOAD | | | CURRENT APPROVAL. OR MANUFACTURER MAY | | | APPLY FOR LOCAL PRODUCT APPROVAL USING | | | THE DADE COUNTY NOA AND COMPLETING THE | | | LOCAL PRODUCT APPROVAL FORM DOWNLOADED | | | FROM THE DCA WEBSITE CITED ABOVE. | | | | | | 4- OWES $26.20 FOR UPDATED VALUE. VALUE | | | WAS UPDATED TO $3810. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|