| 2006-03-29 00:00:00 | | | | THE MANUAL TRANSFER SWITCH'S THIRD POLE | | | DISCONNECTING THE NEUTRAL WOULD APPEAR | | | TO ALSO DISCONNECT THE GROUNDING | | | ELECTRODE CONDUCTOR SYSTEM. UNLESS THE | | | GENERATOR NEUTRAL IS CONNECTED TO THE | | | GEC IN THE OPTIONAL MODE , IT WOULD BE | | | NECESSARY TO ESTABLISH A GROUNDING | | | SYSTEM AT THE GENERATOR, COMPLYING WITH | | | ALL PROVISIONS OF ARTICLE 250.52 AND | | | 250.66. | | | IT WOULD BE BETTER APPLICATION TO | | | INSTALL A 2POLE DISCONNECTING THE | | | UNGROUNDED CONDUCTORS AND LEAVE THE | | | GROUNDED CONDUCTOR SOLIDLY CONNECTED TO | | | THE GEC. | | | | | | PLEASE SUBMIT DOCUMENTS INDICATING A 2 | | | POLE SWITCH OR INDICATING COMPLIANCE | | | WITH 250.52 FOR A SEPERATELY DERIVED | | | SYSTEM. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|