| Notes |
| Date |
Text |
| 2005-11-16 00:00:00 | | | | PLEASE SUBMIT GENERATOR MANUFACTURER | | | SPECIFICATIONS FOR REVIEW. NOTE THAT | | | 2(TWO) COPIES ARE NEEDED AS WITH ALL | | | DOCUMENTS SUBMITTED FOR REVIEW, PER | | | 104.2.1,FBC. | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT A CALCULATION FOR THE | | | INTENDED LOAD OF THE GENERATOR TO BE | | | TRANSFERRED TO THE 30 CKT PANEL SHOWN ON | | | THE PLAN. SEE GEN SPEC'S FOR MAX AND | | | USEABLE OUTPUT (PROBABLY 80%). | | | THE 38.2KW TOTAL HOUSE LOAD SOBMITTED IS | | | TOO LARGE FOR A 20KW GENERATOR. | | | | | | 2} PLEASE LOCATE THE SERVICE AND | | | GENERATOR ON THE SITE PLAN SO THAT | | | COMPLIANCE WITH ARTICLE 225 CAN BE | | | DETERMINED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | | | | |
|