| Date |
Text |
| 2006-02-04 00:00:00 | PLUMBING PLAN REVIEW EXAMINER |
| | PAUL SCHMITZ 561-805-6692 |
| | [email protected] |
| | FBC PLUMBING 2001 |
| | \DENIED 2ND TIME |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PREVIOUS PLAN REVIEW NOTES BY JOHN LEECH |
| | DATED 11-30-05 NOT ADDRESSED. |
| | DENIED; |
| | 1.SHOW WATER RISER DIAGRAM, SIZE ALL |
| | PIPES. |
| | 2.IF BOTH APTS. ON SAME WATER SERVICE A |
| | BACKFLOW PROVENTOR IS REQUIRED, IF NOT |
| | 2ND FLOOR APT. NEEDS A WATER HEATER. |
| | 3.SHOW DIAMETER OF WATER HEATER AND THE |
| | OPENING. MUST BE ABLE TO REMOVE W/H FOR |
| | REPLACEMENT. |
| | 4.SANITARY RISER DIAGRAM NOT TO CODE. |
| | (MARKED IN RED) |
| | A.WET VENT SIZE SEE TABLE 909.3 |
| | B.W/M MUST BE DOWN STREAM OF BATH- |
| | ROOM GROUP SEC.909.1 |
| | C. CLEANOUT ON W/M STACK TO BE |
| | 48" AFF. |
| | 5.IS W/M IN COMMAN AREA FOR 2ND FLOOR |
| | USES? SEE TABLE 403.1(7) |
| | PLUMBING PLAN REVIEW BY; |
| | JOHN LEECH |
| | 805-6695 |
| | ADDITIONAL COMMENTS |
| | 1) PERMIT APPLICATION.DISCRIPTION OF |
| | WORK, AND PLANS SUBMITTED APTS #1,2 |
| | SHOULD INCLUDE BUILDING #1 ON THE |
| | APPLICATION. |
| | 2)ENERGY CALCULATIONS SUBMITTED ARE FOR |
| | SIX UNITS,THREE BUILDINGS. PLEASE |
| | CLARIFY.OR REMOVE FROM SUBMITTED PLANS. |
| | 3)VOIDED SHT.M-2, WAS REMOVED FROM RED |
| | LINED PACKAGE. THIS IS REFERENCED IN |
| | NOTE (4) PREVIOUS COMMENTS. |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |