| 2006-01-30 00:00:00 | ************** UNSAT 2ND REVIEW ******* |
| | |
| | |
| | ** PLEASE SEE MANY NOTESFROM PREVIOUS |
| | REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| | PLEASE ALSO SEE NEW NOTES DUE TO CHANGES |
| | IN PLANS. |
| | |
| | |
| | 1) NOTE: NOTE # 1 OK. |
| | |
| | 2) NOTE: NOTE #2 OK. |
| | |
| | 3)NOTE: NOTE #3 NO, PLEASE SEE LOCATIONS |
| | REDLINED ON PLANS. |
| | |
| | ** PLEASE SEE 210.52D, WHICH |
| | REQUIRES THE GFI RECEPTS WITHIN 3' OF |
| | SINK'S EGDE. PLEASE SEE MISSING ON |
| | REDLINED PLANS.PLEASE ALSO SEE THESE MAY |
| | NOT PLACED AS TOCROSS OVER SINK TO GET |
| | TO RECEPT. |
| | PLEASE EITHER ADD ONE OR MOVE EXISTING |
| | SHOWN. |
| | PLEASE ALSO INDICATE ALL AS GFI. 210.8A1 |
| | |
| | 4)NOTE: NOTE #4 NO, PLEASE SEE MANY SD'S |
| | WERE ADDED, HOWEVER, PLEASE SEE SD |
| | MISSING AT THE TOP OF STATIRWAY AND ON |
| | LOWER LEVEL. |
| | |
| | **SMOKE DETECTORS ARE REQUIRED INSIDE |
| | AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER: NFPA-72 11.5.1.1 |
| | |
| | 5) NOTE: NOTE #5 NO, PLEASE SEE MANY |
| | MISSING. |
| | |
| | ** PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | PLEASE SEE REDLINED PLANS FOR MANY |
| | MISSING. |
| | |
| | 6 ) NOTE: NOTE #6 NO. |
| | |
| | ** PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 7)NOTE: NOTE #7 OK, HOWEVER PLEASE SEE |
| | DISC'S NOW SHOWN FOR CU'S DO NOT MEET |
| | 110.26 |
| | |
| | 8 )NOTE: NOTE #8 NO. |
| | |
| | ** PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5 |
| | PLEASE SEE MANY MISSING, PLEASE ALSO SEE |
| | WHAT APPEARS TO BE ISLAND SHOWS A |
| | J-BOX?? |
| | |
| | 9)NOTE: NOTE #9 NO,PLEASE SEE THE |
| | FOLLOWING COMMENTS FOR LIGHTING |
| | REQUIRED. |
| | |
| | ** PLEASE SEE J-BOXES ARE SHOWN IN |
| | MANY ROOMS, HOWEVER, PLEASE INDICATE IF |
| | THESE ARE GOING TO BE "FAN" J-BOXES. |
| | |
| | 10)NOTE: NOTE #10 NO, PLEASE SEE ROOMS |
| | AND AREAS ARE SHOWN WITH J-BOXES , |
| | HOWEVER LT FIXTURES OF SOME SORT WILL BE |
| | REQUIRED. PLEASE SEE LS 101 7.8.1.3 |
| | WHICH REQUIRES A MIN OF 10FT CANDLES |
| | DURING NORMAL POWER AND PLEASE SEE |
| | 7.9.1.3 WHICH REQUIRES AN EM FIXTURE TO |
| | PROVIDE A MIN OF 1FT CANDLE OF LT TO THE |
| | PUBLIC RIGHT OF WAY. |
| | |
| | ** PLEASE SEE MISSING EGRESS LIGHTING AT |
| | FIRST FLR APT PLANS, APPEARS TO BE SHOWN |
| | ON 2ND FLR? |
| | PLEASE ALSO SEE EGRESS CONTROL REQUIRED |
| | ON MULTI-LEVELS/LANDING. |
| | 210.70 |
| | |
| | 11)NOTE: NOTE #11 OK. |
| | |
| | 12)NOTE: NOTE #12 OK. |
| | |
| | 13)NOTE: NOTE # 13 OK. |
| | |
| | 14)NOTE: NOTE #14 OK. |
| | |
| | 15)NOTE: NOTE #15 OK/ NO, PLEASE SEE |
| | THESE WERE ADDED , HOWEVER PLEASE SEE |
| | EQUIPMENT GROUNDING CONDUCTORS ARE NOW |
| | SHOWN BEFORE THE FIRST MEANS OF |
| | DISCONNECT. PLEASE SEE THESE ARE ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT.250.6 |
| | |
| | ** PLEASE INCLUDE ALL EQUIPMENT |
| | GROUNDING CONDUCTORS WHERE REQUIRED. |
| | 250.110,250.122, 250.24 |
| | |
| | 16)NOTE: NOTE #16 NO, PLEASE SEE A SIZE |
| | WAS ADDED FOR GUTTER, HOWEVER PLEASE SEE |
| | THIS AS BEING SHOWN 8"X 8" AND BY 4"?? |
| | |
| | **PLEASE INDICATE THE MIN SIZE OF |
| | GUTTER PER 366 |
| | |
| | 17)NOTE: NOTE #17 OK, HOWEVER PLEASE SEE |
| | AN ADDITIONAL GRND ROD WILL BE REQUIRED. |
| | |
| | |
| | **PLEASE SEE 250.66 FOR MIN SIZE |
| | OF THE GROUNDING ELECTRODE CONDUCTOR. |
| | |
| | 18)NOTE:NOTE #18 OK. |
| | |
| | NEW NOTES: |
| | |
| | 1)NOTE: PLEASE SEE WATER HEATER ON FIRST |
| | FLR IS BEING SHOWN WITH A RECEPT FOR THE |
| | CONNECTION. PLEASE SEE422.31 WHICH |
| | REQUIRES A DISCONNECT. |
| | |
| | 2)NOTE: PLEASE SEE DRYER DOES NOT |
| | INDICATE ANY RECEPT? |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONALS AND PLANS WITH REPEAT CODE |
| | COMMENTS 3 OR MORE TIMES. |
| | PLEASE SEE THIS IS ONLY ATTACHED THIS |
| | TIME AS A NOTICE. |
| | |
| | |
| | *** PLEASE SEE MOST OF THE ABOVE ITEMS |
| | ARE REDLINED ON ONE OF THE SETS OF PLANS |
| | FOR NOTES ABOVE. |
| | |
| | **PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| | PLANS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |