| 2005-10-18 00:00:00 | ************ UNSAT ************* |
| | |
| | 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 2) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | MUST BE 20A AND #12. |
| | |
| | 3)NOTE: PLEASE SEE 210.52D, WHICH |
| | REQUIRE STHE GFI RECEPT PLEASE SEE |
| | MISSING ON REDLINED PLANS.PLEASE ALSO |
| | SEE THESE MAY NOT PLACED AS TOCROSS |
| | OVER SINK TO GET TO RECEPT. |
| | PLEASE EITHER ADD ONE OR MOVE EXISTING |
| | SHOWN. |
| | PLEASE ALSO INDICATE ALL AS GFI. 210.8A1 |
| | |
| | 4)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER: NFPA-72 11.5.1.1 |
| | |
| | 5) NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | PLEASE SEE REDLINED PLANS FOR MANY |
| | MISSING. |
| | |
| | 6 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 7)NOTE: PLEASE SEE PLANS ARE MISSING THE |
| | LOCATION OF CU'S ALONG WITH MISSING |
| | DISC;S PER 440.11 AND GFI'S PER |
| | 210.8,210.63 |
| | |
| | 8 )NOTE: PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5 |
| | PLEASE SEE MANY MISSING, PLEASE ALSO SEE |
| | WHAT APPEARS TO BE ISLAND SHOWS A |
| | J-BOX?? |
| | |
| | 9)NOTE: PLEASE SEE J-BOXES ARE SHOWN IN |
| | MANY ROOMS, HOWEVER, PLEASE INDICATE IF |
| | THESE ARE GOING TO BE "FAN" J-BOXES. |
| | |
| | 10)NOTE: PLEASE SEE MISSING EGRESS |
| | LIGHTING AT FIRST FLR APT PLANS, APPEARS |
| | TO BE SHOWN ON 2ND FLR? |
| | PLEASE ALSO SEE EGRESS CONTROL REQUIRED |
| | ON MULTI-LEVELS/LANDING. |
| | 210.70 |
| | |
| | 11)NOTE: PLEASE LIST ALL THE REQUIRED |
| | ARC FAULT CIRCUITS ON PANEL SCHEDULE. |
| | PLEASE SEE 2002 NEC 210.12, WHICH |
| | REQUIRES ARC FAULT FOR ALL OUTLETS IN |
| | BEDRMS. |
| | |
| | 12)NOTE: PLEASE SIZE SERVICE ENT |
| | CONDUCTORS FOR SERVICE AND LOAD |
| | PROVIDED.240.4 SEC'S ARE NOT LARGE |
| | ENOUGH. |
| | |
| | 13)NOTE: PLEASE SEE PANELS ARE BEING |
| | SHOWN AS 150A WITH 158 LOAD, AND BEING |
| | FED FROM A 125A DISC????? |
| | PLEASE CORRELATE ALL TO MIN REQUIRED BY |
| | CODE. |
| | PLEASE ALSO SEE #4'S SHOWN FROM GUTTER |
| | TO MAINS. THESE ARE ONLY REATED FOR |
| | 85A'S?? |
| | 240.4,310.16, 215.5, 90.7 ETC. |
| | |
| | 14)NOTE: PLEASE INDICATE WHAT APPEARS TO |
| | BE ADDITIONAL DISCONNECT SON RISER |
| | DIAGRAM?? THESE ITEMS ARE NOT LABELED. |
| | |
| | 15)NOTE: PLEASE INCLUDE ALL EQUIPMENT |
| | GROUNDING CONDUCTORS WHERE REQUIRED. |
| | 250.110,250.122, 250.24 |
| | |
| | 16)NOTE: PLEASE INDICATE THE MIN SIZE OF |
| | GUTTER PER 366 |
| | |
| | 17)NOTE: PLEASE SEE 250.66 FOR MIN SIZE |
| | OF THE GROUNDING ELECTRODE CONDUCTOR. |
| | |
| | 18)NOTE: PLEASE SHOW ALL SERVICE |
| | EQUIPMENT ON PLANS. |
| | |
| | 215.5 |
| | |
| | **PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| | PLANS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |