| 2006-03-24 00:00:00 | *** DENIED *** |
| | 1) MANUFACTURE'S SPECIFICATION'S FOR THE |
| | GAS CLOTHES DRYER AND THE GAS FIRE PLACE |
| | SHOW NO DIRECT VENTING TO PROVIDE |
| | COMBUSTION AIR TO THE UNIT, THEY ONLY |
| | PROVIDE VENTING FOR EXHAUST. |
| | |
| | 2) REQUESTING FOR THE SECOND TIME, |
| | PLEASE PROVIDE COMBUSTION AIR AND/OR |
| | COMB. AIR CALCULATIONS FOR THE GAS |
| | CLOTHES DRYER & GAS FIRE PLACE, PER 2004 |
| | FBC/R M1703 . |
| | |
| | 3) REQUESTING FOR THE SECOND TIME, REFER |
| | TO YOUR MANUAL J AND LOOK UNDRE MIN. & |
| | MAX. VELOCITY, AND CORRECT DUCT SIZES. |
| | EXAMPLE, AHU#2 SUPPLY DUCT IS 14" @ |
| | 1,900 CFM'S THE VELOCITY IS 1,780. |
| | MANUAL J STATES MAX. VELOCITY IS 1,100. |
| | PLEASE CORRECT ALL SUPPLY AIR DUCTS |
| | USING YOUR MANUAL J AS A REFERENCE. |
| | |
| | 4) REQUESTING FOR THE SECOND TIME, |
| | RETURN AIR GRILL 30X18 TO AHU #1 IS TO |
| | SMALL FOR A 5 TON UNIT, PLEASE CORRECT. |
| | |
| | 5) PLEASE SEE ATTACHED NOTICE (FS |
| | 553.80(2)(B). |
| | |
| | 6) PLEASE CHECK WITH THE MANUFACTURE'S |
| | SPECIFICATIONS ON COPPER LINE SIZES, 7/8 |
| | APPEARS TO SMALL FOR A 5 TON SYSTEM. |
| | |
| | MECHANICAL PLAN REVIEW BY; |