| Plan Review Notes For Permit 05100303 |
| Permit Number |
05100303 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-02-14 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE MANUFACTURERS | | | SPECIFICATIONS FOR THE GENERATOR AND | | | TRANSFER SWITCH. | | | | | | 2} SMOKE DETECTORS ARE REQUIRED TO BE | | | INSTALLED IN THE GAME ROOM ( SINCE IT IS | | | COMPARTMENTED FROM THE REST OF THE UPPER | | | FLOOR, AND THEREFORE OTHER DETECTORS) | | | AND ON THE FIRST FLOOR. FBC RES. 313.1 | | | | | | 3} THE PANEL(A)INDICATES IT IS 400 AMP | | | RATED, THE RISER INDICATES 200 AMPS. | | | PLEASE CORRELATE. | | | | | | 4} PLEASE CHECK AND CORRELATE THE A/C | | | AND AHU LOADS WITH THE MECHANICAL PLAN. | | | NOTE THE COMPRESSER LOADS ARE SHOWN | | | LARGER THAN THE AHU LOADS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|