| Notes |
| Date |
Text |
| 2005-11-22 00:00:00 | DENIED; | | | 1.TANKLESS GAS WATER HEATER TO BE | | | INSTALLED ON OUT SIDE NOT IN THE GARAGE. | | | 2.RISER DOES NOT REFECT THE FLOOR PLAN. | | | 3.POTTERY SINK NOT SHOWN ON RISER | | | DIAGRAM. | | | 4.KITCHEN SINK CANNOT DISCHARGE INTO THE | | | WET VENT OF A BATHROOM GROUP FBC-2004 | | | PLUMBING SECTION 909.1. KITCHEN SINK | | | CANNOT BE INSTALLED AS DRAWN. | | | 5.BAR SINK ON 2ND FLOOR REQUIRES A VENT | | | IF INSTALLED AS SHOWN ON RISER DIAGRAM. | | | SEC906.1 | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|