| 2005-11-19 00:00:00 | ----------------DENIED------------------ |
| | |
| | 1. GAS DRYER IN LAUNDRY IS IN A CONFINED |
| | SPACE PER 2004 FBC,R SEC.G2407.5.1. |
| | COMBUSTION AIR MUST BE PROVIDED AS |
| | PRESCRIBED IN SEC 2407.5.3 OR 2407.6. |
| | |
| | 2. PLAN CALLS FOR TWO GAS TANKLESS WATER |
| | HEATERS, BOTH WITH INDOOR LOCATIONS. |
| | PROVIDE MANUFACTURER'S |
| | SPECS/INSTALLATION INSTRUCTIONS TO SHOW |
| | THESE TO BE APPROVED FOR INDOOR |
| | INSTALLATION OR REVISE PLAN TO SHOW |
| | OUTDOOR INSTALLATION LOCATIONS. IF |
| | TANKLESS WH IS TO REMAIN IN LAUNDRY |
| | ROOM, BE SURE TO INCLUDE THE ADDITIONAL |
| | BTUS IN THE CALCULATIONS FOR REQUIRED |
| | COMBUSTION AIR. |
| | |
| | 3. IN MASTER BATH, THE REQUIRED EXHAUST |
| | FAN IS LOCATED IN THE TOILET ROOM, |
| | ISOLATING IT FROM THE REST OF THE MASTER |
| | BATH. ARCHITECTUAL DRAWINGS DO NOT SHOW |
| | A WINDOW IN THIS AREA TO ALLOW FOR AN |
| | EXCEPTION TO THE BATH EXHAUST |
| | REQUIREMENT.AN ADDITIONAL FAN IS |
| | REQUIRED IN THE MAIN AREA OF THE MASTER |
| | BATH. |
| | |
| | 4. PLAN CALLS FOR EXHAUST FAN IN LAUNDRY |
| | ROOM.IS THIS FOR CODE COMPLIANCE |
| | PURPOSES? THE CREATION OF NEGATIVE |
| | PRESSURE IN THIS ROOM MAY ADVERSELY |
| | EFFECT THE EFFICIENT COMBUSTION OF GAS |
| | APPLIANCES AT THIS LOCATION. |
| | |