| 2005-11-15 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE PROVIDE MANUFACTURERS |
| | SPECIFICATIONS FOR THE GENERATOR AND |
| | TRANSFER SWITCH. |
| | |
| | 2} THE #5 BARE COPPER GEC IS NOT A AWG |
| | SIZE. GEC MUST BE A MINIMUM OF #1/0 PER |
| | 250.66. |
| | |
| | 3} THE GROUNDING ELECTRODE SYSTEM MUST |
| | COMPLY WITH 250.50. 250.52(A)(3) |
| | INDICATES HOW THE GEC MUST BE CONNECTED |
| | TO BUILDING (FOOTER) STEEL, PLEASE |
| | INDICATE SAME ON THE PLAN. |
| | |
| | 4} INDICATE DISCONNECTING MEANS PER |
| | 230.71. THE PANELS SHOWN ON THE RISER DO |
| | NOT SPECIFY MAIN BREAKERS. |
| | |
| | 5} PLEASE SHOW THE LOCATION OF ALL |
| | SERVICE AND GENERATOR EQUIPMENT ON THE |
| | FLOOR PLAN. THE RISER SHOWS A GUTTER, |
| | THIS AND THE TRANSFER SWITCH ARE NOT |
| | LOCATED ON THE PLAN, AND PANELS ARE |
| | SHOWN INSIDE? |
| | |
| | 6} PLEASE SIZE THE GUTTER SO THAT |
| | COMPLIANCE WITH ARTICLE 366 CAN BE |
| | DETERMINED. |
| | |
| | 7} PLEASE NOTE THE GENERATOR MUST BE |
| | GROUNDED PER MANUFACTURERS SPEC'S.THIS |
| | IS NOT A SEPARATELY DERIVED SYSTEM AND |
| | MUST USE THE SERVICE NEUTRAL AND GROUND, |
| | THE GENERATOR NEUTRAL CANNOT BE BONDED |
| | TO THE FRAME AND THEN TO A ROD. THIS IS |
| | JUST A NOTE AS IT HAS BEEN BROUGHT TO MY |
| | ATTENTION BY CONTRACTORS THAT THESE |
| | MODELS HAVE A JUMPER FROM THE NEUTRAL TO |
| | THE FRAME, WHICH OF COURSE MUST BE |
| | REMOVED WHEN USING A TWO POLE SWITCH. |
| | |
| | 8} REGARDING CIRCUIT A8, PLEASE SEE |
| | 210.11(C)(3) 20 AMP.THAT CIRCUIT IS |
| | CONFINED TO A SINGLE BATHROOM OR TO ALL |
| | BATH GFI'S ONLY. THE GFI'S IN THE |
| | LAUNDRY MUST NOT BE ON THAT CIRCUIT. |
| | ALSO NOTE 1 GFI IN THE MASTER BATH IS ON |
| | B4. |
| | |
| | 9} CIRCUIT #2, PANEL A, DINING ROOM |
| | RECEPTACLES MUST COMPLY WITH 210.5(B)(1) |
| | & (2), LIVING ROOM CANT BE ON THAT |
| | CIRCUIT. |
| | |
| | 10} ALL OUTLETS, INCLUDING LIGHTING, |
| | RECEPTACLES, FANS AND SMOKE DETECTORS |
| | INSTALLED IN BEDROOMS MUST BE ARC FAULT |
| | PROTECTED PER 210.12. SEE DEFINITION OF |
| | "OUTLET" IN ARTICLE 100 FOR |
| | CLARIFICATION OF 210.12. |
| | |