| Plan Review Notes For Permit 05100256 |
| Permit Number |
05100256 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-22 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE TRANSFER SWITCH MUST BE SERVICE | | | RATED AND CONTAIN A MAIN PER 225.36. | | | PLEASE SUBMIT MANUFACTURERS | | | SPECIFICATIONS FOR SAME. | | | | | | 2} SHOW THE LOCATION OF ALL EQUIPMENT ON | | | THE SITE PLAN SO THAT COMPLIANCE WITH | | | ARTILES 225.31 THROUGH 225.37 CAN BE | | | DETERMINED. | | | | | | 3} THE PERSON RESPONSIBLE FOR THE | | | PLANS MUST PRINT NAME AND SIGN SAME. | | | 104.2.1 FBC. | | | | | | 4} THE LOAD MUST NOT EXCEED THE RATING | | | OF THE GENERATOR, SEE 702.5. THE LOAD | | | CALC IS 120 AMPS AND THE MAX OUTPUT IS | | | 104 AMPS. PLEASE CHOOSE LOADS TO BE USED | | | AND ISOLATE SAME AS GENERATOR LOAD ONLY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|