| Plan Review Notes For Permit 05100239 |
| Permit Number |
05100239 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-13 00:00:00 | *** DENIED *** | | | 1) RETURN AIR IS REQUIRED IN BEDROOMS, | | | YOU MAY ACHIEVE THIS BY TRANSFER GRILLS | | | IN WALLS OR DOORS. PER 2004 FBC/R | | | M1602.4 . | | | 2) DRAIN LINES NOT SHOWING ON PLANS. PER | | | FBC/R M1411.3 . | | | 3) PLANS ARE CALLING FOR A 34,000 BTU | | | A/C SYSTEM AND MANUAL 'J' IS CALLING FOR | | | 21,119 BTU'S OF COOLING THE TWO MUST | | | COINCIED. | | | 4) PLEASE SHOW ON PLANS WHERE DOORS AND | | | OPENINGS IN WALLS ARE. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|