| 2006-03-01 00:00:00 | ********** UNSAT 3RD REVIEW ********** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS TWO REVIEWS. |
| | |
| | |
| | |
| | 1)NOTE: NOTE #1 OK |
| | |
| | |
| | 2)NOTE: NOTE #2 OK |
| | |
| | 3)NOTE:NOTE #3 OK/ NO, PLEASE SEE ONLY |
| | ONE SHEET WAS REVISED AND 2ND FLR PLANS |
| | ARE THE SAME PLANS FROM PREVIOUS REVIEW. |
| | |
| | **PLEASE VERIFY LOCATION OF |
| | PANELS, BOTH APT UNITS DOWN STAIRS SHOWS |
| | PANELS INSIDE UNITS, HOWEVER UPSTAIRS |
| | UNITS DO NOT INDICATE PANELS? |
| | PLEASE SEE 240.24 FOR LOCATION OF |
| | ACCESSIBILITY TO OCCUPANTS FOR OCP>. |
| | 215.5 |
| | PLEASE ALSO SHOW LOCATION OF SERVICE ON |
| | PLANS AS AN ELECTRICAL ROOM IS SHOWN, |
| | HOWEVER SERVICE IS NOT SHOWN.? |
| | 215.5 |
| | |
| | 4)NOTE:NOTE #4 NO, PLEASE SEE RECEPTS DO |
| | NOT MEET 210.52C1. |
| | PLEASE SEE DISPOSAL IS STILL BEING SHOWN |
| | AS GFI? |
| | |
| | ** PLEASE SEE PLANS ONLY INDICATE |
| | THE DIPOSAL AND DISHWASHER. BOTH OF |
| | THESE ARE SHOWN AS GFI? PLEASE SEE NO |
| | APPLIANCE GFI RECEPTS ARE SHOWN, YET |
| | THESE ARE REQUIRED. 210.52C1, 210.8A6 |
| | |
| | 5)NOTE: NOTE #5 NO, PANEL SCHEDULE NOW |
| | INDICATES A ARC FAULT CIRCUIT, YET THIS |
| | IS SHOWING ALL DEVICES IN BOTH BEDRMS, |
| | LTS, SD'SRECEPTS ONLY ONE ONE CIRCUIT? |
| | PLEASE SEE PREVIOUS PANEL SCHEDULE AND |
| | THIS PANEL SCHEDULE INDICATES MORE THAN |
| | 5 GEN LT CIRCUITS?? |
| | |
| | **PLEASE SEE PLANS INDICATE ARC |
| | FAULT BEING ADDED TO BEDRMS, HOWEVER |
| | PANEL SCHEDULE DOES NOT SHOW THIS? |
| | PLEASE KNOW, RECEPTS DO NOT COME AS |
| | BEING ARC FAULT TYPE AS GFI'S ARE. THE |
| | ONLY ARC FAULT PROTECTION AT THIS TIME |
| | IS THE BRANCH BRKR. |
| | |
| | 6)NOTE: NOTE #6 OK. |
| | |
| | 7)NOTE: NOTE #7 OK |
| | |
| | 8)NOTE: NOTE #8, OK, THIS SHALL BE FEILD |
| | VERIFIED. |
| | |
| | |
| | 9)NOTE:NOTE #9 NO,PLEASE SEE NOT ALL |
| | NEW PLANS WERE SUBMITTED. PLEASE ALSO |
| | SEE THE SET OF OLD/VOIDED SHEETS |
| | SUBMITTED FOR REFERENCE ARE FROM ANOTHER |
| | PERMIT AND NOT THIS PROJECT. |
| | ** PLEASE KNOW, IF ALL COMMENTS ARE NOT |
| | ADDRESSED A 4X FEE WILL BE ACCESSED. |
| | |
| | ****PLEASE SEE 553.80(2)(B) IN |
| | FLORIDA STATUES. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | |
| | NEW NOTE: |
| | |
| | 1)NOTE: PLEASE ADJUST NOTE ON PLANS WITH |
| | RESPECT TO SCOPE OF WORK AND WHAT |
| | DEVICES ARE BEING REPLACED AND WHAT |
| | AREAS ARE BEING REMODELED/RE-WIRED. |
| | PLEASE SEE KITCHEN AREA SHALL MEET ALL |
| | CURRENTS CODES AS THIS ARE IS BEING |
| | REPLACED WITH NEW CABINETS. |
| | PLEASE SEE CENTRAL AIR IS BEING ADDED , |
| | IF CEILINGS ARE BEING OPENED, THEN A 20A |
| | CIRCUIT WILL BE REQUIRED FOR BATHRM |
| | (210.11C3 AND RECEPT SPACING ON TWO |
| | INNER WALLS WILL REQUIRE SPACING PER |
| | 210.52. |
| | |
| | 2)NOTE: PLEASE SEE PLANS ARE BEING SENT |
| | TO BLDG AS ENERGY CALCULATIONS SUBMITTED |
| | BACK WITH PLANS ARE NOT COMPLETE, NOT |
| | FILLED OUT COMPLETELY, SIGNED, DATED |
| | ETC. |
| | IF THERE ARE CALCS WHICH WERE DONE |
| | CORRECTLY AND STAMPED ON PREVIOUS |
| | REVIEW, PLEASE BRING THOSE BACK IN TO |
| | THE BLDG REVIEWER ASAP. |
| | |
| | |
| | **PLEASE SEE ANY COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. ONE COPY OF OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |