Plan Review Notes
Plan Review Notes For Permit 05100207
Permit Number 05100207
Review Stop M
Sequence Number 3
Notes
Date Text
2006-08-10 00:00:00MECHANICAL REVISION
 *** DENIED ***
 1) RETURN AIR TRANSFER DUCT TO MASTER
 SUITE NEEDS TO BE 12" PER 2004 FBC/R
 M1602.4 .
  
 2) ARCHITECT'S LICENSE NUMBER MUST
 APPEAR IN TITLE BLOCK, PER FAC
 61G1-16.003 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.