Plan Review Notes
Plan Review Notes For Permit 05100207
Permit Number 05100207
Review Stop E
Sequence Number 1
Notes
Date Text
2005-11-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}PLEASE SUBMIT AIC RATINGS FOR ALL
 NEW SERVICE EQUIPMENT BEING INSTALLED.
 MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9.
  
 2} INCLDE BUILDING STEEL IN THE
 GROUNDING ELECTRODE SYSTEM. SEE 250.50.
  
 3} INCLUDE THE BATH CIRCUIT ON THE PANEL
 SCHEDULE PER 210.11(C)(3).
  
 4} THE MASTER BATH REQUIRES A RECEPTACLE
 FOR THE SECOND SINK. SEE 210.52(D).
  
 5} THE BATH RECEPTACLES MUST BE GFI
 PROTECTED PER 210.8(A)(1).
  
 6} THE GARAGE IS REQUIRED TO HAVE A
 RECEPTACLE PER 210.52(G). ALSO GFI PER
 210.8(A)(2).
  
 7} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST BE GFI PER 210.8(A)(6), ALSO SPACED
 PER 210.52(C)(1).
  
 8} A RECEPTACLE NEEDS TO BE ADDED AT THE
 DOORWAY OF THE MASTER BEDROOM PER
 210.52(A)(2), ALSO IN THE LIVING ROOM
 PER 210.52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  