| Plan Review Notes For Permit 05100207 |
| Permit Number |
05100207 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-09 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1}PLEASE SUBMIT AIC RATINGS FOR ALL | | | NEW SERVICE EQUIPMENT BEING INSTALLED. | | | MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9. | | | | | | 2} INCLDE BUILDING STEEL IN THE | | | GROUNDING ELECTRODE SYSTEM. SEE 250.50. | | | | | | 3} INCLUDE THE BATH CIRCUIT ON THE PANEL | | | SCHEDULE PER 210.11(C)(3). | | | | | | 4} THE MASTER BATH REQUIRES A RECEPTACLE | | | FOR THE SECOND SINK. SEE 210.52(D). | | | | | | 5} THE BATH RECEPTACLES MUST BE GFI | | | PROTECTED PER 210.8(A)(1). | | | | | | 6} THE GARAGE IS REQUIRED TO HAVE A | | | RECEPTACLE PER 210.52(G). ALSO GFI PER | | | 210.8(A)(2). | | | | | | 7} THE KITCHEN COUNTERTOP RECEPTACLES | | | MUST BE GFI PER 210.8(A)(6), ALSO SPACED | | | PER 210.52(C)(1). | | | | | | 8} A RECEPTACLE NEEDS TO BE ADDED AT THE | | | DOORWAY OF THE MASTER BEDROOM PER | | | 210.52(A)(2), ALSO IN THE LIVING ROOM | | | PER 210.52(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|