1 |
|
| Notes |
| Date |
Text |
| 2005-10-12 00:00:00 | *** DENIED *** | | | 1) PLANS DO NOT COINCIDE WITH ENERGY | | | CALCULATIONS ON FILE. ENERGY CAL'S. ARE | | | CALLING FOR 3 A/C SYSTEMS TOTALING 10 | | | 1/2 TONS, PLANS ARE CALLING FOR 4 A/C | | | SYSTEMS TOTALING 13 1/2 TONS. | | | 2) RETURN AIR DUCTS ARE NEEDED IN THE | | | DINING ROOM & LIBRARY. PER 2001 FBC/M | | | 601.4 . | | | 3) RETURN AIR DUCT IN MASTER BEDROOM | | | NEEDS TO BE 16" . PER 2001 FBC/M 601.4 . | | | 4) POOL HOUSE NEEDS DUCT SIZES FOR | | | RETURN AND SOME SUPPLY AIR DUCTS. | | | 5) CONDENSATE DRAIN LINES NOT SHOWING. | | | PER 2001 FBC/M 307.2 . | | | 6) BATHROOM EXHAUST FANS NOT SHOWING. | | | PER 2001 FBC/M 402.3.1 . | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|