| 2005-12-01 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- PROVIDE FLORIDA PRODUCT APPROVAL OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL (FBC |
| | 2004 AS OF OCTOBER 1ST 2005)FOR |
| | ACCORDION SHUTTERS AND CLEAR SHUTTERS AS |
| | REQUIRED BY RULE 9B-72 OF DCA. GO TO |
| | WWW.FLORIDABUILDING.ORG FOR INFORMATION |
| | REGARDING PRODUCT APPROVALS. |
| | ***NOTE: DADE COUNTY NOA ALONE IS NOT |
| | AUTOMATICALLY AN STATE WIDE FLORIDA |
| | PRODUCT APPROVAL. IF MANUFACTURER HASN'T |
| | APPLIED FOR FLORIDA PRODUCT APPROVAL, |
| | THEN, MANUFACTURER MAY APPLY FOR LOCAL |
| | PRODUCT APPROVAL USING THE DADE COUNTY |
| | NOA AND COMPLETING THE LOCAL PRODUCT |
| | APPROVAL FORM DOWNLOADED FROM WEBSITE |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | 2- A) LOOKOUT SHUTTERS FLORIDA PRODUCT |
| | APPROVAL SUBMITTED NEED TO BE UPDATED TO |
| | COMPLY WITH FBC 2004. MANUFACTURER TO |
| | APPLY FOR UPDATED PRODUCT APPROVAL (OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL). |
| | |
| | B) LOOKOUT SHUTTERS DRAWINGS ARE NOT |
| | LEGIBLE. NEED CLEAR AND LEGIBLE DRAWINGS |
| | C) REMAINDER: CHECK MAX. PANEL SPANS |
| | ACCORDING TO THE DESIGN PRESSURES. |
| | |
| | 3- A) PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE (SEE ATTACHED SAMPLE) AS REQ'D |
| | BY CITY IMPLEMENTATION STANDARD FOR |
| | HURRICANE MISSILE IMPACT PROTECTION AND |
| | SEC.106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | B) CLEARLY MARK IN DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND SPECIFIC ANCHOR |
| | TYPE AND SPACING TO BE USED ACCORDING TO |
| | THE DESIGN PRESSURES, PANEL SPAN, EDGE |
| | DISTANCE, CONNECTION TYPE AND STRUCTURE |
| | TO BE ATTACHED TO (CONCRETE, CONCRETE |
| | BLOCK, WOOD). SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 4- NOTICE OF COMMENCEMENT IS EXPIRED |
| | AFTER 90 DAYS OF RECORDING IF WORK IS |
| | NOT STARTED. SEC. 713.13(2) FL. |
| | STATUTES. NEED RE-RECORDED ONE. |
| | |