| Plan Review Notes For Permit 05100121 |
| Permit Number |
05100121 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-06 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | 1} PLANDS MUST BEAR THE PRINTED AND | | | SIGNED NAME OF THE DESIGNER, SEE 104.2.1 | | | FBC. | | | | | | 2} SUBMIT A RISER DIAGRAM INDICATING THE | | | GROUNDING ELECTRODE SYSTEM AND SIZE OF | | | THAT CONDUCTOR. 250.50 & 250.66. | | | | | | 3} THE CONDUCTORS APPEAR TO BE PASSING | | | THROUGH THE BUILDING FROM THE METER. | | | ARTICLE 230.70 REQUIRES A DISCONNECTING | | | MEANS FOR THE UNGROUNDED CONDUCTORS. | | | SHOW COMPLIANCE WITH A DISCONNECT AT THE | | | NEW METER LOCATION ON THE RISER DIAGRAM. | | | INDICATE THE AMPERAGE RATING OF SAME. | | | | | | 4} THE 1/0 SERVICE CONDUCTORS ARE TOO | | | SMALL FOR THE 200 AMP PANEL THEY ARE | | | SERVING. SEE 310.15(B)(6).,SHOW THE OCP | | | AT THE FIRST MEANS OF DISCONNECT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|