Notes
Date Text
2005-10-06 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} PLANDS MUST BEAR THE PRINTED AND
 SIGNED NAME OF THE DESIGNER, SEE 104.2.1
 FBC.
  
 2} SUBMIT A RISER DIAGRAM INDICATING THE
 GROUNDING ELECTRODE SYSTEM AND SIZE OF
 THAT CONDUCTOR. 250.50 & 250.66.
  
 3} THE CONDUCTORS APPEAR TO BE PASSING
 THROUGH THE BUILDING FROM THE METER.
 ARTICLE 230.70 REQUIRES A DISCONNECTING
 MEANS FOR THE UNGROUNDED CONDUCTORS.
 SHOW COMPLIANCE WITH A DISCONNECT AT THE
 NEW METER LOCATION ON THE RISER DIAGRAM.
 INDICATE THE AMPERAGE RATING OF SAME.
  
 4} THE 1/0 SERVICE CONDUCTORS ARE TOO
 SMALL FOR THE 200 AMP PANEL THEY ARE
 SERVING. SEE 310.15(B)(6).,SHOW THE OCP
 AT THE FIRST MEANS OF DISCONNECT.
  